Notification Appliance Circuit Module

D192G

en

Installation manual

Summary of Contents for D192G

Page 1: ...Notification Appliance Circuit Module D192G en Installation manual ...

Page 2: ......

Page 3: ...roperly installed tested or maintained devices Before installing the module become familiar with the Installation and Operation Guide for the control panel you are using The module uses only polarized DC signaling devices Not all signaling devices are polarized The signaling devices used with the module must be polarized DC signaling devices match the voltage rating of the alarm power supply not e...

Page 4: ...ential burglar units This feature allows the system to support more signaling devices on longer wire runs It also allows the use of 12 V or 24 V notification appliances requiring the appropriate power supply Control panels Compatible modules Compatible relays See section Active Products G series V3 and higher 1 panels D8128D D130 D133 D134 Wiring the module with G Series control panels page 9 B se...

Page 5: ...see Warning below 7 Positive connection to the signaling device loop 3 Connection to control panel zone output 8 Negative connection to the signaling device loop 4 Connection to control panel s programmable alarm outputs 9 Toggle switch for silencing the indicating devices 5 Positive connection to UL 864 certified power supply 10 Mounting holes Warning The D192G common COM terminals are digital gr...

Page 6: ... indicates possible causes for the various LED indicator patterns Indicator Possible cause SUPERVISION TROUBLE LED yellow is on Output loop or 560 Ω EOL resistor is open or missing Alarm switch is in SILENCE OFF position SUPERVISION TROUBLE LED and ALARM LED red are off Normal operation with no alarm or trouble No power Check for voltage across the External Power In and Common terminals If the ext...

Page 7: ...Listed enclosure install the enclosure according to the manufacturer s instructions For UL fire applications mount the module within 20 ft 6 m of the control panel enclosure with the wiring in conduit between the two For multiple modules you can connect up to twelve modules to the same supervision point The point must use a 1 kΩ end of line EOL resistor Install the 560 Ω 2 W EOL resistor beyond th...

Page 8: ...ply must be a UL 864 Listed auxiliary 12 VDC or 24 VDC regulated power limited power supply for fire protective signaling units and commercial or residential burglary units Install the auxiliary supply according to the manufacturer s instructions Install the control panel and an external power supply in the same room no more than 20 ft 6 m apart The interconnecting wiring between the control panel...

Page 9: ...onnected modules to a G Series panel supplying 12 VDC power 1 Last D192G module on the interconnected NAC loop 6 1 kΩ EOL resistor P N F01U011298 2 Polarized notification devices 7 Connection to either Relay A or Relay B programmed output 3 560 Ω 2 W EOL resistors P N F01U008725 8 Connection between module SUPV ZONE and panel zone 4 First D192G module on the interconnected NAC loop 9 Connection be...

Page 10: ... the interconnected NAC loop 7 Connection to Relay A programmed output 2 Polarized notification devices 8 Connection to Relay B programmed output 3 560 Ω 2 W EOL resistors P N F01U008725 9 Connection between module COM and panel s COMMON not to earth ground 4 First D192G module on the interconnected NAC loop 10 Connection between one module s SUPV ZONE terminal and panel zone 5 G Series control pa...

Page 11: ...rnal power supply and module COM to panel s COMMON not to earth ground 2 Polarized notification devices 9 Positive connection between module s ALRM terminal and the power supply 3 560 Ω 2 W EOL resistors P N F01U008725 10 Conduit required for wiring between external power supply and control panel enclosure 4 First D192G module on the interconnected NAC loop 11 Connection to either Relay A or Relay...

Page 12: ...fication devices 9 Positive connection between module s EXT PWR IN terminal and the power supply 3 560 Ω 2 W EOL resistors P N F01U008725 10 Conduit required for wiring between external power supply and control panel enclosure 4 UL Listed 12 VDC or 24 VDC regulated power limited auxiliary power supply 11 Connection to Relay B programmed output to ALRM TRG of the other module 5 G Series control pan...

Page 13: ...ower 1 Last D192G module on the interconnected NAC loop 8 Positive connection between panel s aux power and module s aux and ext power terminals 2 Polarized notification devices 9 Connection to module s ALRM TRG terminal 3 560 Ω 2 W EOL resistors P N F01U008725 10 Connection between module s SUPV ZONE and panel zone 4 First D192G module on the interconnected NAC loop 11 Connection to panel s Aux p...

Page 14: ...nel zone 2 Polarized notification devices 10 Connection between the other module s SUPV ZONE and panel zone 3 560 Ω 2 W EOL resistors P N F01U008725 11 Connection to the panel s Aux power 12 V 4 First D192G module on the interconnected NAC loop 12 D134 Dual Relay Module 5 B Series control panel 13 Positive connection between panel s aux power and the aux and ext power terminals of the modules 6 Co...

Page 15: ...M TRG terminal 2 Polarized notification devices 10 Connection between module s SUPV ZONE and panel zone 3 560 Ω 2 W EOL resistors P N F01U008725 11 Connection to panel s Aux power 12 V 4 First D192G module on the interconnected NAC loop 12 Connection between module COM and panel s digital COM not to earth ground 5 B Series control panel 13 Conduit required for wiring between external power supply ...

Page 16: ...erminal of the power supply 2 Polarized notification devices 12 Connection to panel s Aux power 12 V 3 560 Ω 2 W EOL resistors P N F01U008725 13 Connection between the other module s SUPV ZONE and panel zone 4 First D192G module on the interconnected NAC loop 14 Connection to the other module s ALRM TRG terminal 5 B Series control panel 15 D134 Dual Relay Module 6 Connection to C programmed output...

Page 17: ...Inc Installation manual 2020 05 04 4998122260 9 Connection between one module s SUPV ZONE and panel zone 19 1 kΩ EOL resistor P N F01U011298 10 Connection between both module s COM terminals the power supply s negative terminal and the panel s digital COM not to earth ground ...

Page 18: ... the point using a point index configured as Point Type 0 24 h Pt Response 9 Short Fire Supervision Open Fire Trouble Buzz on Fault 2 Fire Yes Program all other selections for the point index number No 6 2 Alarm output For instructions on programming the control panel refer to the panel s Program Entry Guide For compatibility information about synchronization modules and strobes refer to the panel...

Page 19: ...Current Maximum draw 100 mA Maximum rating of the module alarm circuit 3 A Voltage AUX PWR IN 12 VDC nominal EXT PWR IN 12 VDC or 24 VDC supplied by an external regulated power limited power supply or 12 VDC supplied by the control panel s AUX PWR terminal for special applications Mechanical Dimensions LxWxD 5 in x 3 in x 0 75 in 12 7 cm x 7 6 cm x 1 9 cm ...

Page 20: ...20 Specifications Notification Appliance Circuit Module 2020 05 04 4998122260 Installation manual Bosch Security Systems Inc ...

Page 21: ......

Page 22: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2020 Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany ...