Operation
Condens 7000 WP – 6721842519 (2022/03)
24
▶ Check the tightness and installation/brackets of the flue system.
Fig. 31 Inspecting the gas path
▶ Determine and rectify the cause of a possible leak.
▶ Deactivate
Function check
.
8.10
Check the function of the boiler
▶ Lower the temperature at the connected control and check whether
the boiler starts burning after several minutes to support the boiler
operation.
▶ If applicable: open a DHW tap, check the DHW temperature and
draw-off quantity.
8.11
Completion work
▶ Mount the front cover.
▶ Complete the commissioning report (
8.12
Instructing the operator
▶ Familiarise the user with the heating system and operation of the
boiler.
▶ Point out to the operator that if heating water frequently needs to be
refilled this is a sign that the system is faulty and/or leaking (ensure
required water quality according to the operator's log).
▶ Inform operator about the required water quality and point out where
the heating water must be refilled.
▶ Inform the operator that he or she must not carry out any
modifications or repairs.
▶ Point out the possible consequences (material damage, personal
injury or danger to life) of not carrying out inspection, cleaning and
maintenance correctly, or omitting it altogether.
▶ Draw attention to the dangers associated with carbon monoxide (CO)
and recommend the use of CO detectors.
▶ Hand over the technical documents to the operator.
9
Operation
9.1
Control panel overview
Fig. 32 Control panel
[1]
Display
[2]
and
keys
[3]
Heating water pressure display
[4]
d
key
[5]
OK key
[6]
Menu key
[7]
Hot water key
[8]
Heating key
[9]
Burner display
See the operating instructions for a description of the user menus.
9.2
Switching on the device
▶ Switch on the appliance at the On/Off switch (
Fig. 1, page 6).
Set the language the first time the device is turned on.
▶ To scroll through the languages, press the
or
key.
▶ To select the desired language, press the OK key.
When the display shows
Siphon fill. prog.
, the trap filling program is
active. The condensate trap in the appliance is filled (
Chapter 9.3,
9.3
Siphon filling program
The siphon filling program is activated automatically, manually by the
installer on the device or on the controller. Before starting, fill the
condensate siphon (
Page 15).
The siphon filling program is activated in the service menu under
>
Settings > Special function > Siphon fill. prog.
.
While the siphon filling program is active, access to the
Hot water
menu,
the
Heating
menu and the service menu is possible.
The siphon filling program is activated automatically in the following
cases:
• The device is switched on using the On/Off switch.