Technical information and reports
49
Condens 7000 WP – 6721842519 (2022/03)
16.3
Hydraulic resistances
Table 29 Hydraulic resistances
16.4
Residual head of pumps
Changing the pump output
The standard setting for the pump output is sufficient under normal
conditions or with the heating circuit distributor. With a measured
T of
more than 20 K an adjustment of the pump output is desirable.
▶ Increase the pump output until
T is 20 K (
-or-
▶ Reduce the installation resistance by installing a low loss header.
Fig. 48 Residual head of pump GC7000WP 125, GC7000WP 145
[1]
Maximum adjustable discharge head of pump
[2]
Standard setting of discharge head
[3]
Minimum pump discharge head
[4]
Resistance of heat exc conn non-return valve
[5]
Resistance of heat exc connection set
[6]
Resistance of heat exchanger
16.5
Setting values for heating capacity
Table 30 Setting values for heating capacity
16.6
Commissioning report for the appliance
Unit
GC7000WP 125
GC7000WP 145
Required
volumetric flow
rate at
T = 20 K
l/h
5300
6300
Max. volumetric
flow rate
l/h
7000
Resistance of the
boiler
mbar
312
430
0010041018-002
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
0
1000
2000
3000
4000
5000
6000
[mbar]
[l/h]
1
2
3
6
5
4
Output
Display
Display
GC7000WP 125
GC7000WP 145
[kW]
[%]
[%]
25
20
17
30
24
21
35
28
24
40
32
27
45
36
31
50
40
34
55
44
38
60
48
41
65
52
45
70
56
48
75
60
51
80
64
55
85
68
58
90
72
62
95
76
65
100
80
68
105
84
72
110
88
75
115
92
79
120
96
82
125
100
86
130
--
89
135
--
92
140
--
96
145
--
99
146
--
100
Customer/system user:
Surname, first name
Street, house number
Telephone/fax
Postcode, town
System installer:
Order number:
Appliance type:
(
Complete a separate report for every appliance!
)
Serial number:
Date of commissioning:
Individual appliance |
Cascade, number of devices: ......