Servicing and spares
|
43
6 720 ... ... (YYYY/MM)
Product Name
Fig. 62 Burner removal
[1]
Clip
[2]
Castellated nuts
[3]
Washers/Springs
[5]
Rear nut
[6]
Spacer and washer
[7]
Burner head
[8]
Seal
[9]
Rear stud
[10] Burner
[11] Front studs
For sealed systems only:
Electrical wiring
▶ Check the electrical wiring for physical damage and replace any
damaged wires.
To check the flap valve in the fan intake
▶ Refer to page 48 for access to the fan intake.
▶ Carefully withdraw the flap valve from fan intake tube and check for
soiling and splits, clean or replace as required.
▶ Take care when refitting the flap valve, the flaps must open upwards
into the fan in take tube.
▶ After re-assembly check CO/CO
2
levels as described in the section
“Setting the air/gas ratio”.
To clean the condensate trap
Refer to figure 70 on page 49 to remove the trap
▶ Remove the condensate pipe [1]
▶ Remove the screw retaining the trap [2]
▶ Pull the trap down to remove from the boiler
▶ Remove the bottom cap [3] and empty the condensate and flush out