Service Function Adjustment
|
5
2.2.2
2. Service Level
Operating
Change or query of a service function :
B
To enter to 2. service level must be entered first in 1. level.
Press
button for 5 second. The service function onf1.
level will be shown on Display (e.g. 1.2.C).
B
To enter to 2. level : Press both “
+”
and “
-”
buttons for 3
second. The service function of 2. level will be shown on
Display (e.g. 2.1.A).
B
Select the desired/requested service code with “+” or “-”
button.
B
Press
button again (for entering)..
After that you will see the selected (default) value on Dis-
play.
Changing / Adjustment of Value:
B
Change the values with “+” or “-” button.
Storage/Save of Value :
B
Press
button until
[ ]
symbol will be shown on Display.
Exit from Service level :
B
For the exit from service level press the
or Stand by
button.
The flow temperature will be shown again on display.
2. Level
Service
Code
Description
Range
Initial (Factory Setting)
2.1.A
CH max. heat output
30 - 100 %
100 %
2.1.b
DHW max. heat output (in winter mode)
30 - 100 %
100 %
2.2.b
CH max flow temperature
35 - 82°C
82°C
2.3.d
CH min. heat output
30 - 100 %
30 %
2.3.F
Delay time after DHW in winter mode (Heating mode is disabled for this
period of time)
0 - 5 min.
1 min.
2.8.A
Software version number
e.g.. 162 112
-
2.8.E
Reset to factory (default) setting
0
0
2.9.A
Operation mode permanent : (0 = Normal, 1= min. power, 2 = max.
power)
0 - 2
0
2.9.E
Delay time for the turbine ( each unit = 0,5 sec.)
1 - 6
2
2.9.F
Pump over run) (CH circuit)
0 - 10 min.
3
2.A.A
Actual flow temperature
ºC
-
2.A.b
Actual DHW temperatur
ºC
-
2.A.F
Actual combustion chamber temperature
ºC
-
2.b.d
Selection of flue length (MAP Value) (0 = off, 1 - 10 : fan speed accord-
ing flue pipe length, see flue manuel for details)
0 - 10
0
2.b.F
Solar mode delay time (sec.)
1 - 50
1
2.c.F
Pump "over run” (DHW mode)
0 - 30 sec.
5 sec.
2.0.A
Gas Convertion (0 = NG, 1 = LPG)
0 -1
0
Tab. 2
2. level service functions