8.3 Adding refrigerant
Some systems require additional charging depending on pipe lengths. The standard
pipe length varies according to local regulations.
For example, in North America, the standard pipe length is 7.5m (25’). In other
areas, the standard pipe length is 5m (16‘). The additional refrigerant to be charged
can be calculated using the following formula:
Additional refrigerant per pipe length
Connective Pipe
Air Purging
Additional Refrigerant
< Standard pipe length
Vacuum Pump
N/A
> Standard pipe length
Vacuum Pump
Liquid Side: Ø 6.35 (ø 0.25”)
Inverter R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
Liquid Side: Ø 9.52 (ø 0.375”)
Inverter R410A:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Table 8
CAUTION:
NEVER mix refrigerant types.