Before using your bacnet, please read this manual carefully and keep it for future reference.

CLIMATE 5000 VRF   

Building Management System Gateway Card (Bacnet)

BMS-BAC

User manual

Summary of Contents for BMS-BAC

Page 1: ...6720862469 16 04 Before using your bacnet please read this manual carefully and keep it for future reference CLIMATE 5000 VRF Building Management System Gateway Card Bacnet BMS BAC User manual ...

Page 2: ...CONTENTS 1 CONNECTING DIAGRAM 3 2 FUNCTION DESCRIPTION 3 3 CONFIGURATION ILLUSTRATION 3 4 OBJECT TABEL 4 2 CONTENTS 6720862469 16 04 CLIMATE 5000 VRF ...

Page 3: ...ACnet into a web browser 3 1 Control setting The local network code range will be between 0 and 63 The name of the network will automatically configure which can be changed to something more memorable After the demand has been set and the equipment has been restarted the equipment will modify the changes The control code has been set randomly before ex factory means of control code in CONTROL UNIT...

Page 4: ...onnect 1 and 2 of 485 This will restore factory settings of the BACnet 4 OBJECT TABEL This device provides with different objects tables for the different types of outdoor units which are in using for the VRF system System will automatically identify using outdoor unit and generate the BACnet object 4 1 Indoor objects This equipment provides with fourteen types of BACnet object show as the followi...

Page 5: ...76 R Segmentation support BACnetSegmentation Segmented both 0 R Local Time Time R W Local Date Date R W APDU Segmentation Timeover Unsigned 2000 O APDU Timeover Unsigned 3000 R APDU Resend Times Unsigned 3 R Device Address Binding AddressBinding ASN 1 R Operation instruction The CURRENT VALUE attribute of the selected object reflects the COMPRESSOR 1 ELECTRIC CURRENT it s unsettable The MINIMAL VA...

Page 6: ...lue Unsigned 5 Event enable BACnetEventTransitionBits T T T O Affirm transform BACnetEventTransitionBits T T T O Notify Type BACnetNotifyType alarm O Operation instruction The CURRENT VALUE attribute of the selected object reflects the current FAN SPEED It s writable and settable Thereinto the CURRENT VALUE 1 means HIGH SPEED the CURRENT VALUE 2 means MEDIUM SPEED the CURRENT VALUE 3 means LOW SPE...

Page 7: ...y NO FAULT DETECTED R Take off service BOOLEAN F R Unit BACnetEngineering Units Degree Celsius R Minimum REAL 20 O Maximum REAL 100 O Distinguishability REAL 1 O Time delay Unsigned 1 O Publicly type Unsigned 1701 O Low valve value REAL 20 O High valve value REAL 100 O Width valve value REAL 1 O Enable valve value BACnetLimitEnable T T O Event enable BACnetEventTransitionBits T T T O Notify Type B...

Page 8: ...String Off Time Setting O Status Flags BACnetStatusFlags F F F F R Event states BACnet EventStates Normal R Take off service BOOLEAN F R Unit BACnetEngineering Units Hours R Minimum REAL 0 O Maximum REAL 24 O Distinguishability REAL 0 25 O Reliability BACnetReliability NO FAULT DETECTED O Priority Array BACnetPriorityArra NULL R Default release REAL 0 R COV INCREMENT REAL 0 25 O Low valve value RE...

Page 9: ...ame CharacterString AC _OElecHeat R Object Type BACnetObjectType Binary output R Current value BACnetBinaryPV Inactive W Discription CharacterString Elecheat Setting O Status Flags BACnetStatusFlags F F F F R Event states BACnet EventStates Normal R Take off service BOOLEAN F R Polarity BACnetPolarity Normal R Inactive text CharacterString Turn off O Active text CharacterString Turn on O Time dela...

Page 10: ...e of the selected object reflects the current MALFUNCTION it s read only In case of the CURRENT VALUE shows as No E that means without malfunction while other information displaying means the relevant malfunction For detail please refer to TROUBLESHOOT MAINTENANCE BROCHURE or contact with After sales agent Provided that more the one malfunction occurs simultaneously only the minimal No of the erro...

Page 11: ...s No P 12 Mode query Attribute identifier Data type Attribute value Read Write Object identifier BACnetObjectIdentifier Multistate input 3 R Object name CharacterString AC_QueryMode R Object type BACnetObjectType Multistate input R Description CharacterString QueryMode O Status text BACnet ARRAY N CharacterString Heat Cool Dehumidify Fanonly Auto Stop O 13 Fan speed query Attribute identifier Data...

Page 12: ...n Software Edition CharacterString 1 0 R Protocol Edition Unsigned 1 R Protocol Correspondency Type Unsigned 3 R Protocol Service Support BACnetServiceSupport ReadProperty etc R Protocol Object Types Support BACnetObjectTypesSupport AnalogInput etc R Object Array BACnetArray n List all objects R Max length of APDU support Unsigned 1476 R Segmentation support BACnetSegmentation Segmented both 0 R L...

Page 13: ...serviceBOOLEAN F R States number Unsigned 4 R States text BACnet ARRAY N CharacterString Low Middle High Stop O Time delay Unsigned 1 O Publicly type Unsigned 1701 O Event enable BACnetEventTransitionBits T T T O Affirm transform BACnetEventTransitionBits T T T O Notify Type BACnetNotifyType alarm O Operation instruction The CURRENT VALUE attribute of the selected object reflects the current FAN S...

Page 14: ...1701 O Low valve value REAL 0 O High valve value REAL 250 O Width valve value REAL 1 O Enable valve value BACnetLimitEnable F T O Event enable BACnetEventTransitionBits T T T O Notify Type BACnetNotifyType alarm O Operation instruction The CURRENT VALUE attribute of the selected object reflects the current INDOOR UNIT QUANTITY it s read only 6 Compressor 1 current Attribute Identifier Data mode At...

Page 15: ...elected object reflects the COMPRESSOR 2 ELECTRIC CURRENT it s unsettable The MINIMAL VALUE stands for the minimum electric current while the MAXMUN VALUE stands for the maximum electric current 8 Compressor 3 current Attribute Identifier Data mode Attribute value Read write Object Identifier BACnetObjectIdentifier Analog iutput 5 R Object Name CharacterString AC_ ICom3Current R Object Type BACnet...

Page 16: ... VALUE shows as No E that means the system without protection while other information displaying means the other relevant protection For detail please refer to TROUBLESHOOT MAINTENANCE BROCHURE or contact with After sales agent Provided that more the one protection occurs simultaneously only the minimal No of the protection would be showed Thereinto the CURRENT VALUE displays as 1 means EO the CUR...

Page 17: ...CURRENT VALUE shows as No P that means the system without protection while other information displaying means the other relevant protection For detail please refer to TROUBLESHOOT MAINTENANCE BROCHURE or contact with After sales agent Provided that more than one protection occurs simultaneously only the minimal No of the protection would be showed Thereinto the CURRENT VALUE displays as 1 means P0...

Page 18: ...18 NOTES 6720862469 16 04 CLIMATE 5000 VRF 5 NOTES ...

Page 19: ...CLIMATE 5000 VRF 6720862469 16 04 NOTES 19 ...