Installation, Operation & Maintenance Manual
Bosch 96% AFUE Gas Furnace
| 45
Bosch Thermotechnology Corp.
|
04.2019
Data subject to change
When using a single stage thermostat, second stage delay is based on the setting of
switch S1-1, S1-2 shown below.
Option Switches S1-1 & S1-2 Positions
Delay Time:
On "S1" set switch #
1
2
Off *
Off
Off
10 min
On
Off
Auto min
Off
On
20 min
On
On
Table 22
2nd Stage Delay For Single Stage Thermostats
* Factory default setting– two stage thermostat
2. Cooling Mode (if applicable)
In a typical single stage cooling system (Y connection), a call for cool is initiated by
closing the thermostat contacts. This energizes the compressor and the electronic
air cleaner (optional).
The circulator will be energized at cool speed after the COOL delay-to-fan-on
period. After the thermostat is satisfi ed, the compressor is de-energized and the
COOL delay-to-fan-off period begins. After the COOL delay-to-fan-off period ends,
the circulator and the electronic air cleaner are de-energized.
3. FAN Mode
If the thermostat fan mode is set to ON, the circulator fan (low heat speed) and
optional electronic air cleaner are energized. When the fan mode is returned to
AUTO, the circulator fan and electronic air cleaner (optional) are deenergized.
11.5 Gas Manifold Pressure Measurement and Adjustment
NOTICE:
To prevent unreliable operation or equipment damage,
the gas manifold pressure must be as specifi ed on the unit
rating plate. Only minor adjustments should be made by
adjusting the gas valve pressure regulator.
This valve is shipped from the factory with the regulator preset to 3.5 in. WC.
Consult the appliance rating plate to ensure burner manifold pressure is as
specifi ed. If another outlet pressure is required, follow these steps (see Table 23
and Fig. 37):
1.
Turn OFF all electrical power to the system.
2.
Using a 3/32 inch hex wrench, loosen outlet pressure tap screw one turn.
Do not remove screw.
3.
Attach a hose and manometer to the outlet pressure barb fi tting of valve to
overlap at least 3/8”
4.
Turn ON system power and set thermostat to a call for heat.
5.
Using a leak detection solution or non-chlorine soap suds, check for leaks at
hose connection. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX
ALL LEAKS IMMEDIATELY!
6.
Remove burner access panel.
7.
Remove regulator screw cover. Turn regulator screw either clockwise to
increase pressure or counter clockwise to decrease. Always adjust regulator
to provide the correct pressure according to the original equipment
manufacturer specifi cations listed on the appliance rating plate.
8.
Replace regulator screw cover and fi nger-tighten securely.
9.
Turn OFF all electrical power to the system.
10.
Remove manometer and hose from outlet pressure tap.
11.
Tighten outlet pressure tap clockwise 7 in-Ibs minimum to seal port.
12.
Replace burner access panel.
13.
Turn ON system power and set thermostat to call for heat.
14.
Using a leak detection solution or non-chlorine soap suds, check for leaks at
hose connection. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX
ALL LEAKS IMMEDIATELY!
Figure 37
HIGH FIRE COIL TERMINAL (HI)
COMMON TERMINALS (C)
COAXIAL COIL
TERMINAL (M)
ON/OFF SWITCH
INLET PRESSURE
TAP
MANIFOLD PRESSURE
TAP
REGULATOR VENT
LOW FIRE
REGULATOR
ADJUSTMENT
HIGH FIRE
REGULATOR
ADJUSTMENT
Regulator
Cover
Screw
Regulator
Spring
Plastic
Regulator
Adjustment
Screw
Regulator
Sleeve
Gas valve and regulator adjustment
15.
Measure gas manifold pressure with burners fi ring. Adjust manifold
pressure per the Manifold Gas Pressure table.
Input
Rating
KBTU/H
Furnace Model
Range Orifi
ce
Size
Natural
Gas
Propane
Gas
Natural
Gas
Propane
Gas
60
BGH96M060B3A
3.5" W.C
10" W.C
45
55
80
BGH96M080B3A
3.5" W.C
10" W.C
45
55
80
BGH96M080C4A
3.5" W.C
10" W.C
45
55
100
BGH96M100C5A
3.5" W.C
10" W.C
45
55
100
BGH96M100D5A
3.5" W.C
10" W.C
45
55
120
BGH96M100D5A
3.5" W.C
10" W.C
45
55
Table 23
Manifold Gas Pressure
The fi nal manifold pressure must not vary more than ± 0.3 in. WC from specifi ed
manifold pressure.
Any necessary major changes in gas fl ow rate should be made by changing the size
of the burner orifi ce.