AVENAR panel
Planning | en
29
Bosch Sicherheitssysteme GmbH
System manual
2022-07 | 5.0 | F.01U.378.910
–
Cable length of up to 3000 m
–
As stipulated by EN 54-2, panels with more than 512 detectors and manual call points
must be equipped with a redundant panel controller. Combined with an AVENAR panel
8000, an AVENAR keypad 8000 can be used as a redundant panel controller.
3.2
Detection points
Each element or input that can trigger an alarm counts as an detection point. One stand-alone
panel manages up to 4096 detection points. A panel operated in a network is limited to 2048
points.
All elements and inputs that do not use the Input type in the Message type setting are
regarded as detection points. Therefore, all elements and inputs for which one of the
following settings is programmed as the Message type are regarded as detection points:
–
Fire
–
Internal fire
–
Supervisory
–
Multi-criterion
–
Smoke
–
Fault
–
Heat
–
Water
Only some of these message types are available for selection depending on the element type.
The elements and inputs that can trigger an alarm include all manual and automatic detectors,
as well as the modules and interface modules listed below on the basis of the available inputs.
Modules
Detection Points
CZM 0004 A
Up to 4 (1 detection point per zone)
IOP 0008 A
Up to 8 (1 detection point per monitored input)
RMH 0002 A
Up to 2
ENO 0000 B
requires 1 detection point only if a FSE release element is
connected and programmed using the FSP-5000-RPS
programming software
FPP‑5000‑TI
2
Interface Modules
Detection Points
FLM-420/4CON
Up to 2
FLM-420-I8R1
Up to 8
FLM-420-I2
Up to 2
FLM-420-O8I2
Up to 2
FLM-420-O1I1
Up to 1
FLM-420-RHV
Up to 2
FLM-420-RLE-S
Up to 2