![Bosch AVENAR 4000 FAH-425-T-R Operation Manual Download Page 7](http://html.mh-extra.com/html/bosch/avenar-4000-fah-425-t-r/avenar-4000-fah-425-t-r_operation-manual_43072007.webp)
–
Increased detection and false alarm security thanks to evaluation of the temporal
behavior of fire and disturbance variables.
–
Activation of a remote indicator is possible.
–
Optional mechanical removal safeguard (can be activated/deactivated).
–
Dust-resistant labyrinth and cap construction.
–
Every detector base has a Chamber Maid Plug (a cleaning opening with a plug) for
blowing out the optical chamber with compressed air (not required for the FAH-425-T-R
Heat Detector).
–
For connecting to the FPA-5000 and FPA-1200 fire panels with extended range of LSN
features.
–
In classic mode, can be connected to the BZ 500 LSN, UEZ 2000 LSN and UGM 2020 LSN
fire panels and to other panels or their receiver modules with identical connection
properties but with the existing LSN system limits.
–
It is possible to read out the serial number, contamination level (for the O sensor),
operating hours, EMC strength level and current analog values for each configured
detector via LSN.
–
Use of shielded and unshielded cables.
–
The LSN improved version line technology supports the connection of up to 254 FAP-425/
FAH-425 series detectors per loop or stub (please observe national regulations in this
regard).
–
Flexible network structures without additional elements are possible (T-tapping is not
feasible with detector versions without rotaries).
–
Automatic or manual detector addressing selectable.
–
Compliant with EN 54, EN 50131 and VdS guidelines.
For DO detectors, note:
Notice!
The device cannot be used with the FPA-5000 type A panel controller.
Accessories
FLM-320-EOL2W EOL Module
FLM-320-EOL2W EOL Module
The FLM-320-EOL2W EOL module is a 2-wire module for
terminating a line according to EN 54-13.
The module detects faults according to EN 54-13 and
reports errors to the fire panel.
Support Plates
The support plates are made from 1.8 mm thick ABS plastic and are clamped between the
detector base and the ceiling.
2.5
AVENAR detector 4000
System Overview | en
7
Bosch Sicherheitssysteme GmbH
Operation Guide
2014.11 | 1.1 | F.01U.283.550
Summary of Contents for AVENAR 4000 FAH-425-T-R