Mode
Terminal connection
Alarm condition
1
+
The remote indicator shows steady red light. Current has
to be limited to max. 30 mA.
2
+
The remote indicator shows steady red light. Input voltage
range: 8.5 V DC … 33 V DC. Constant current consumption
13 mA.
3
+
The remote indicator shows flashing red light. Input voltage
range: 11 V DC … 33 V DC. Constant current consumption
3 mA.
Operate in mode 1 and 3 only, when connected to LSN detectors.
1.
Place the cap on the base plate in such a way that the two hooks are inserted into the
slits.
2.
Press the cap lightly onto the base plate until the snap‑fit‑hook engages.
Notice!
Malfunction
The cable length between the detector and the remote indicator must not exceed 3 m when
connected by an unshielded cable.
Technical specifications
FAA‑420‑RI‑ROW
FAA‑420‑RI‑DIN
Operating Voltage
5 ‑ 30 V DC
9 ‑ 30 V DC
Maximum current
consumption
20 mA
Mode 1: limited to 30 mA
Mode 2: 13 mA
Mode 3 : 3 mA
Permissible wire gauge
0,6 – 2 mm
0,6 ‑ 0,8 mm
Display medium
1 LED
2 LED
Dimensions
85 x 85 x 28 mm
85 x 85 x 35 mm
Weight
45 g
65 g