AMC2 4W | Installation manual
F.01U.024.965 | V 0.1 | 2006.03
Bosch Sicherheitssysteme GmbH
6.2
Configuring the Ethernet Interface
To configure the AMC2 4W in a TCP/IP network environment
use the tool
AmcIpConfig
provided in the following directory :
\\Runtime-drive:\MgtS\AccessEngine\AC\bin
This tool can be copied and used on every computer.
6.3
Resetting the AMC2 4W
When a problem occurs, first, try to fix the problem directly. If
this does not solve the problem, resetting the AMC2 4W may
help:
1.
Insert the provided screwdriver into the hole as shown in
the figure below.
2.
Push the reset button for at least three seconds.
3.
The AMC2 4W will be reset and reboots. You are back in
the download program.
4.
Now it is possible to reconfigure the AMC2 4W from the
beginning.
5.
If the problem still arises, please, call your local service.
Resetting the network configurations:
1.
Reset the AMC as described above (in download program)
2.
Open the upper case of the AMC2 4W
3.
Set all six DIP switches of the RS-485 selector to ON
4.
Press the tamper switch on the upper left side of the board
The AMC2 4W will now have the following network configura-
tion:
•
DHCP = 0
•
IP = 127.0.0.1
i
NOTE!
The usage of the software application to configure the AMC2
4W via Ethernet interface is described in the online help of the
tool.