15. Changing basic settings
i
The set values guarantee that the ACS 810 will
function perfectly. These parameters may only be
changed by an A/C service unit engineer and after
approval from the manufacturer.
!
Follow the additional ACS 810 menu prompting.
1.
Call up the start screen.
2.
Press <
3
> and <
Flush
> simultaneously and release.
The message
ENTER CODE 0000
is displayed.
3.
Enter
5599
and confirm with
E
.
4.
Select the
relevant parameter
with
o
u
and
confirm with
E
.
i
Return with <
Stop
>.
Parameter Actions
Default
P1
System pressure empty.
Absolute pressure value above which
recovery begins.
1700
P2
Pressure at end of recovery.
Absolute pressure value above which
recovery ends.
600
P3
Vacuum test pressure.
Absolute pressure value after which
the vacuum test turns out to be
negative.
300
T1
Vacuum pump oil change threshold.
Number of hours before a prompt to
change the vacuum pump oil appears
on the display.
30
T2
Time for automatic emptying.
Value in seconds for duration of
automatic emptying.
140
T3
Maximum time for recovery.
If this time is exceeded, the function
is aborted and the message "LONG
EXTRACTION TIME" appears on the
display.
120
T4
Weight variation monitoring threshold
Time in seconds in which the weight
(recovered quantity) must change
during recovery, otherwise the
operation is aborted.
60
T5
Oil outlet time. Time in minutes for the
oil drainage duration.
5
T7
Specified time for vacuum. The
mean time recommended by car
manufacturers is 20 minutes.
60
T8
Not used.
–
T9
Vacuum test duration.
Time for checking any pressure
increase after the vacuum function has
been executed.
300
T10
Recycling plus vacuum time.
Time in minutes for the duration of the
recycling plus vacuum function.
10000
T13
Maximum time for the filling process.
If this time is exceeded, the function
is aborted and the message "FILLING
INCOMPLETE" appears on the display.
50
Parameter Actions
Default
T16
Maximum time for the flushing
process.
If this time is exceeded, the function is
ended and the process continues.
15
T20
Vacuum test time for flushing
operation.
Time in seconds for the vacuum test
duration in the flushing function.
120
T21
EV7 oil outlet open duration.
Time in seconds for which the solenoid
valve EV7 remains open during the oil
outlet function.
240
W1
Combo filter replacement threshold.
Value in kilograms before a prompt to
replace the combo filter appears on
the display.
150
W6
Max. capacity of small bottle.
Value in grams that represents the
maximum quantity for filling the small
internal refrigerant cylinder.
10000
W8
Max. capacity of large bottle.
Value in grams that represents the
maximum quantity for filling the large
internal refrigerant cylinder.
35000
HOSE
CLEANING
TIME
Minimum time for cleaning the service
hoses. This is the minimum value in
seconds for emptying the service hoses
after filling.
90
CONTROL
REPORT
Activates and deactivates the "Save
data via ACUSB PC interface" function.
0 (off)
COMPEN-
SATION
AT 0
Activates and deactivates the
"Compensation at 0 in filling phase"
function (i.e. compensation is
deactivated).
0 (off)
BYPASS
Activates and deactivates the "Bypass"
function. If this function is activated,
the MENU key skips the waiting times
for the main ACS 810 functions.
0 (off)
ECOLD
2006
Konfiguration Leiterplatte.
Wert muss "1" betragen.
1
RENAULT
CONFIG
Mode required by Renault.
The times between two recoveries are
extended. This mode can be activated
or deactivated as required
0 (off)
BACKUP
See section "Data Backup".
–