Diagnostics and Testing
Will Not Inject Oil
1. Verify the oil injection bottle is securely
attached and contains an appropriate
amount of oil.
2. Verify a vacuum has been pulled on the
system.
3. Verify the high-side service hose is properly
attached to the unit without any restrictions
and coupler valve is open.
4. Open service menu and go into
Output
test
to activate the oil inject solenoid (S14) and
HS inlet solenoid (S5).
5. Verify power to the oil inject solenoid (S14)
and HS inlet solenoid (S5).
6. Verify the solenoid coil is opening the
solenoid properly.
• With the system pulled into a vacuum,
remove the oil bottle, place a finger over
the end of the oil inject tube and activate
the oil inject solenoid. Suction should be
felt at the oil inject tube.
• If no suction is felt, the oil inject solenoid
may not be receiving power. Check the
continuity of the wiring between solenoid
and power board. Repair as needed.
• If the wiring is correct and no power is
being applied to the solenoid, replace
the power board.
7. Verify operation of the oil inject check valve.
Replace as needed.
Will Not Charge
NOTE:
There is no component that pumps
refrigerant into a system during the charge
process. The refrigerant flows due to a pressure
differential. If the system is not in a vacuum,
unit will not charge.
1. Verify the service hoses are properly
attached to the unit without any restrictions
and coupler valves are open.
2. Verify a deep vacuum has been pulled on
the system being charged.
3. Check that all ISV hoses are properly
installed and check Tank Liquid solenoid
(S7) for debris.
4. Verify the scale has been calibrated.
5. INSUFFICIENT REFRIG AVAILABLE will be
displayed if the weight entered leaves less
than 1.0 kg of refrigerant in the internal tank
after charge. If there is enough refrigerant
in the tank, check scale calibration and
recalibrate if necessary.
6. Verify the low-side inlet (S4), high-side inlet
(S5) and tank liquid (S7) solenoids are
receiving power and opening properly.
• If not receiving power, check the continuity
of the wiring between solenoid and power
board. Repair as needed.
• If the wiring is correct and no power is
being applied to the solenoid, replace the
power board.
NOTE:
If the unit does not complete a full
charge, the compressor is switched on and off
to build tank pressure.