Controls | 43
6 720 813 643 (2018/04)
▶ Access menu
PA
.
▶ Touch symbol
OK
.
▶ Touch symbols
or
to select
MF main valve
.
▶ Touch symbol
OK
.
The appliance will start the auto calibration of main valve.
▶ Touch the symbol
to return to main menu.
5.8.2 BP bypass valve auto calibration
▶ Open one hot water tap.
Flow rate between 0.80 GPM and 1.80 GPM is required.
It's possible to confirm this value by entering the BP bypass menu (see below).
▶ Access menu
PA
.
▶ Touch symbol
OK
.
▶ Touch symbols
or
to select
BP bypass valve
.
▶ Touch symbol
OK
.
The appliance will start the auto calibration of the bypass valve.
▶ Touch the symbol
to return to main menu.
Water flow will shut-off.
▶ Wait until indication of calibration completed appears on the
screen.
The display shows the flow rate.
▶ You should adjust the flow rate at the beginning of the
calibration process.
▶ Wait for the indication that the calibration is completed to
appear on the screen.