OMD91046 rev D
26
4.4
POSITIONING AND INSTALLATION
The UPS must be installed in a clean and dry room, preferably not dusty. The User
must ensure that there is enough air exchange in the room so that the equipment can
be adequately cooled. If this is not guaranteed, the room must be adequately cooled.
In case the UPS contains batteries inside (10-15-20kVA), adequate air exchange
must be ensured as provided for by EN62040-1, annex N.
4.4.1 Base plan, static load and weights
Picture 20 – Base plan
UPS (kVA)
10 15 20
30
40
50
60
B8031FXS/B8033FXS B8033FXS
L1 – mm
450
P1 – mm
650
L2 – mm
-
B8031FXS (kVA)
10
15
20
Weight w/o battery - kg
100
110
110
Weight with battery - kg
Min. 175
Max. 285
Min. 260
Max. 285
Min. 260
Max. 285
Static load w/o batteries – kg/m2
315 348 348
Static load with batteries – kg/m2
Min. 470
Max. 945
Min. 829
Max. 895
Min. 829
Max. 895
B8033FXS
(kVA)
30 40 50 60
Weight w/o battery - kg
140 140 170 170
Weight with battery - kg
350 350 -
-
Static load w/o battery – kg/m2
464 464 563 563
Static load with battery – kg/m2
1160 1160
-
-