User’s Manual
33
6.
E
NGINEERING
D
ATA
6.1. R
ATINGS
C
HARTS
Table 6-1: Model M3534R Ride-Thru Module Ratings
M
ODEL
N
UMBER
AC
I
NPUT
M
AX
.
O
UTPUT
P
OWER
R
ECOMMENDED
F
USE
R
ATINGS
(AC
I
NPUT
/
DC
O
UTPUT
)
M
AX
.
DC
O
UTPUT
C
URRENT
M3534R-L006-A5
230 VAC
6kW /8hp
A60Q30-2 / A70Q25-2
20 ADC
M3534R-E010-A5
400 VAC 10kW /13hp
A60Q30-2 / A70Q25-2
20 ADC
M3534R-H012-A5
460 VAC 12kW /16hp
A60Q30-2 / A70Q25-2
20 ADC
Table 6-1 Notes:
Table 6-2: Model M3534R Ride-Thru Module Voltage Levels
AC
I
NPUT
V
OLTAGE
DC
B
US
V
OLTAGE
L
EVELS
T
HRESHOLD
M
IN AT
F
ULL
L
OAD
N
OMINAL
208VAC
265 VDC
255 VDC
290 VDC
230VAC
285 VDC
275 VDC
320 VDC
380 / 400 / 415VAC
485 VDC
475 VDC
535
– 565 VDC
460VAC
585 VDC
575 VDC
640 VDC
Table 6-2 Notes:
The
Min at Full Load
column in the table above lists the minimum voltage level at which the DC
bus will be maintained when the RTM is active. This is usually about 90% of the nominal DC bus
level, and 7-10V
below the THRESHOLD where “activity” begins.
The
NOMINAL
column in the table above lists the normal operating DC bus voltage level.
Table 6-3: De-Rating Table
S
YSTEM
V
OLTAGE
R
ATING
C
ODE
AC
L
INE
V
OLTAGE
K
W
R
ATING
L
208 VAC
5 kW
230 VAC
6 kW
E
380 VAC
9 kW
400 VAC
10 kW
415 VAC
10 kW
H
433 VAC
11 kW
460 VAC
12 kW