11.1
Control via
contacts/remote contacts
In operation mode “Control via contacts” or “Control via remote contacts” (Parameter
Local/Remote
412 = 0 or 2), the frequency inverter is controlled directly via digital in-
puts or via the individual bits of the virtual digital signals in the control word. The func-
tion of these inputs is described in the frequency inverter user manual.
Control word (
Local/ Remote
412 = 2)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
STOA and STOB
1
IN1D
2
IN2D
3
IN3D
4
IN4D
5
IN5D
6
MFI1D
7
MFI2D
8
-
9
-
10
-
11
-
12
-
13
-
14
-
15
-
The digital inputs set via the control word can be monitored using parameter
Digital
Inputs
250. Digital input S1IND will only be displayed if controller release is switched
on at STOA and STOB and the control word (Bit 0) was set. If the data set switching
function is used, please ensure that Parameter
Local/Remote
412 is set to “2 – Con-
trol via remote contacts” is set in all data sets used.