C H A P T E R 2 - S O F T W A R E
6
Alarm Config tab settings
Distance Units
•
Select Miles or Kilometers by clicking on the corresponding radio button
Red Lightning Alarm
•
The Red strike alarm is always active and cannot be disabled.
•
The
Strike Enable
distance box cannot be set to the same or exceed an Orange or Yellow
enabled strike alarm distance. The set distance cannot exceed 20 miles/32km using just the
EFM-100 sensor or 40 miles/64km with coincidence mode enabled.
•
The
Active For
box sets the duration that the Red alarm will remain active when a strike is
detected within the set distance range. This value can be set between 1 and 60 minutes.
•
The
High Field Enable
box enables/disables a Red High Field alarm.
•
The
Above
box is used to set the desired magnitude of the electrical field to activate
the alarm and represents the same positive and negative field levels. This value
cannot be the same or less than an active orange or yellow high field alarm.
•
The
Delay On
time is the length of time the set electric field magnitude must
remain above before the alarm is activated. If the electric field magnitude drops
below the set point before the delay expires, the delay timer will be reset. This value
can be set between 1 and 600 seconds.
•
The
Active For
box sets the duration that the Red alarm will remain active when
this high field alarm is activated. This value can be set between 1 and 60 minutes.
Orange Lightning Alarm
•
The Orange strike alarm can be enabled or disabled.
•
The
Strike Enable
distance box cannot be set to the same or lower distance than the Red
strike alarm. The set distance cannot exceed 20 miles/32km using just the EFM-100 sensor
or 40 miles/64km with coincidence mode enabled.
•
The
Active For
box sets the duration that the Orange alarm will remain active when a
strike is detected within the set distance range. This value can be set between 1 and 60
minutes.
•
The
High Field Enable
box enables/disables an Orange High Field alarm.
•
The
Above
box is used to set the desired magnitude of the electrical field to activate
the alarm
and represents the same positive and negative field levels. This value
cannot be the same or lower than the active Yellow high field alarm level. It also
cannot be set to the same level or higher than the Red high field alarm if enabled.
•
The
Delay On
time is the length of time the set electric field magnitude must
remain above before the alarm is activated. If the electric field magnitude drops
below the set point before the delay expires, the delay timer will be reset. This value
can be set between 1 and 600 seconds.
•
The
Active For
box sets the duration that the Red alarm will remain active when
this high field alarm is activated. This value can be set between 1 and 60 minutes.