4.2.3 Routine Testing 

4.2.3.1 Routine  testing  of  detector  operability  is  performed  by  simulating  of  the  Test/Fire 
mode  (depending  on  the  current  setting)  and  Trouble  mode  by  means  of  relevant  buttons 
incorporated in remote control unit and duplicated in the detector. 

4.2.3.2 The relevant button TEST or TROUBLE shall be pressed and held pressed at least for 
five seconds. 

6  GETTING STARTED 

In  order  the  detector  to  operate  under  a  polling  loop  controller  in  an  Orion  ISS,  it  should  be 
assigned  to  a  polling  loop  address  and  relevant  settings  should  be  carried  out  (see  User/s 
Manual).

 

Summary of Contents for S2000-IPDL

Page 1: ... necessary to comply with safety measures in accordance with Regulations for Operation of Consumers Electrical Installations and Safety Rules for Operation of Consumers Electrical Installations While installing and maintaining the detector please comply with the rules for working at heights 2 MOUNTING 2 1 The units of the detector should be attached to the building structures generally with the he...

Page 2: ...he detector enable connecting wires with cross section area 0 2 to 1 5 sq mm wire diameter 0 5 to 1 3 mm If wires of 0 8 mm diameter or less are used then their ends shall be looped 2 8 The housing of the transceiver unit can be removed if only there are no locking screws in the latches at the top and the bottom of the housing To remove the housing release both the latches pressing on them and pul...

Page 3: ...0 m Range 30 to 120 m 25 to 100 m 20 to 80 m S2000 IPDL Transceiver Mounting Kit 5 to 120 m Reflector Four elements max Mounting Kit Rotated by 90 Remote Indicator and Control Unit Rotated by 90 S Type Reflector XS Type Reflector 1 Dimensions for information 2 The distance between Transceiver Unit and Remote Indicator and Control Unit should not exceed 30 m ...

Page 4: ... at least 5 second until the red indicator illuminates The panel PC shall display the events of loss of communication with the device assigned with an old address and finding a device with the new address If several devices were assigned with equal addresses set then there will be no messages about loss of communications for old addresses 4 3 If however it is necessary to change the detector addre...

Page 5: ... second one If you failed to alter this performance then with great probability the detector is improper 5 1 6 If the detector exits the alignment mode normally it shall enter in the Norm state indicating this by red flashing once per four seconds 5 1 7 Arm the detector 5 1 8 Press the TROUBLE button on the detector s board and observe fast flashing with amber Trouble in Progress followed by flash...

Page 6: ... after exiting the alignment mode Норма Norm with Switched from time to time with green flashes Establishing of the Test status after pressing the relevant button with amber flashes Establishing of the Trouble status after pressing the relevant button with white flashes Trouble in Progress Conditions for some Trouble status have occurred but this status has not yet been established Набор Неис Trou...

Page 7: ...obscuration for the reflecting surface and moreover L Type reflectors are equipped with an additional scale at their lower edges which is to be used when the reflectors are arranged with two ones in a row 4 2 2 2 Since the S2000 IPDL is a single ended detector and optical beam crosses the monitored area twice then for simulating the beam degradation by a required value the percentage of obscuratio...

Page 8: ...nt buttons incorporated in remote control unit and duplicated in the detector 4 2 3 2 The relevant button TEST or TROUBLE shall be pressed and held pressed at least for five seconds 6 GETTING STARTED In order the detector to operate under a polling loop controller in an Orion ISS it should be assigned to a polling loop address and relevant settings should be carried out see User s Manual ...

Reviews: