MOUNTING AND WIRING THE MODULE 

2.1

 

Mounting the Module 

2.1.1

 

Mount  the  module  in  line  with  the  Russian  regulatory  document 

РД

.78.145-92  “Rules  for  Manufacturing  and  Commissioning.  Fire  and 

Intrusion  Alarm  Installations”.  Mount  the  module  at  a  height  above  the  floor 
which is suitable to operate and maintain the device. 

2.1.2

 

The  module  is  to  be  mounted  on  walls  or  other  constructions  of 

premises  at  places  protected  against  atmospheric  fallouts  and  mechanical 
damage. 

2.1.3

 

Prior to attaching the module, please ensure that the wall the module 

is to be mounted to is solid, flat, and dry. 

2.1.4

 

Mark points on the wall for four mounting holes in accordance with 

Figure 1. 

2.1.5

 

Drill  the  mounting  holes.  Then  insert  wall  plugs  into  the  holes  and 

screw  two  woodscrews  provided  in  the  two  upper  holes  so  that  the  distance 
between a woodscrew head and the wall is about 7 mm. 

2.1.6

 

Remove the right-side cover panel. 

2.1.7

 

Hang  the  module  on  two  woodscrews.  Screw  the  remaining 

woodscrew into the lower side mounting hole and fix the module on the wall. 

Figure 2.

 Opening 

Cover Panel 

 

2.2

 

Wiring the Module 

2.2.1

 

Connect wires to the terminals as shown in Figure 3. 

2.2.2

 

Please observe polarity while connecting the module to the power supply. 

2.2.3

 

The cross section of wires should not exceed 1.5 sq. mm. 

2.2.4

 

If the  module, the control panel, or other Orion system devices connected to the RS-485 

interface  bus  are  supplied  with  power  by  different  power  supplies  then  couple  their  relevant  “0V” 
circuits. 

2.2.5

 

Unless the module is the last or the first device in the RS-485 interface bus, remove the 

EOL jumper from the module’s PCB (see Figure 3). 

2.2.6

 

If necessary connect the external reader to the module as shown in Figure 3. 

The  module  does  not  provide  monitoring  communication  lines  with  the  reader  for  good 

conditions, so fire-fighting installations should not be operated by means of the reader connected to 
the module. 

2.2.7

 

Close the cover panel of the module (see Figure 2). 

 
 
 
 
 
 
 
 

                         

 

 

 

 

 

Figure 3. 

External Connection Diagram 

PS: Primary and (optionally) backup 10.2…28.4 V dc power supplies 

+

 

S2000M Panel 

Orion ISS 

connection interface 

S2000 Panel

+

 

Orion Pro 

Software

 

To PS 

iButton Reader 

Buzzer 

Tamper Switch 

 

620 

 EOL Jumper 

RS-485 

LED R 
LED GRN 

0V 

B

 

A

 

0V 

ТМ

 

Summary of Contents for S2000-BI Rev.02

Page 1: ... to be operated in aggressive and dusty environments and in ex hazardous premises 1 2 Specifications Light Indication 60 two color LEDs to indicate conditions of up to 60 partitions of Orion ISS 8 single color LEDs to display alarms and troubles in Orion ISS One LED to indicate the module conditions One LED to show that a sound is silenced One LED to show whether or not operating by iButton is per...

Page 2: ...2 S2000 BI S2000 BI Rev 02 Figure 1 View and Overall and Mounting Dimensions of the Module ...

Page 3: ... fix the module on the wall Figure 2 Opening Cover Panel 2 2 Wiring the Module 2 2 1 Connect wires to the terminals as shown in Figure 3 2 2 2 Please observe polarity while connecting the module to the power supply 2 2 3 The cross section of wires should not exceed 1 5 sq mm 2 2 4 If the module the control panel or other Orion system devices connected to the RS 485 interface bus are supplied with ...

Page 4: ...e 4 shows the display of the S2000M panel with the relevant message 3 5 8 If several messages accumulated by the module have been received by the panel you can browse them by the arrow buttons and on the S2000M 3 6 Testing Indication in Self Diagnostic Mode Indication Test 3 6 1 Initiate the self diagnostic mode by starting the indication test from the network controller 3 6 2 The module s indicat...

Page 5: ...ring Access Control Security Alarm 3 Sound Alarms for Fire 2 Fire Prealarm Sound alarms can be disabled if the S2000M network controller is located near the module Disabled or On for indefinite time On 4 Sound Alarm Duration for Trouble Condition The time on elapsing which a sound alarm will be silenced automatically Sound alarms can be disabled if the S2000M network controller is located near the...

Page 6: ...op troubles troubles of outputs power failures communication loss etc Fault Input Open Failure Input Short Failure Configuration Error Tamper Alarm Output Open Failure Output Short Failure Mains Failed Overload Battery Test Error Power Failed Charger Failed Battery Failed Low Battery Low Backup Battery Level Above Limit Level Below Limit Noise Actuator Failure Actuator Error Service Required Tempe...

Page 7: ...n amber with S2000M of version 3 00 Note The indication type Security 3 Alarm operates correctly only if the control panel S2000M of version 2 03 or higher is in use The indication type Fire Alarm is meant to indicate conditions of individual fire partitions zones The integrated indicators Fire Trouble and Disabled of the modular fire alarm control and indicating equipment are located of the S2000...

Page 8: ...ed only by S2000M control panels of versions 2 07 The indication types Auxiliary Auxiliary 2 and Auxiliary 3 are expected for signaling about conditions of various engineering equipment doors etc which are monitored by means of auxiliary alarm loops The types Auxiliary and Auxiliary 2 imply that the relevant partition contains only auxiliary alarm loop and various troubles of this loop are indicat...

Page 9: ...h red 0 5 s On 0 5 s Off Normal Temperature Normal Level Lit steady in green Disabled Lit steady in amber The indication type Leakage Monitoring is used to warn about flooding Table 13 Performance of LEDs 1 60 for Indication Type Leakage Monitoring Partition Status Indicator 1 60 Performance Flooding Alarm Pulses with red 0 5 s On 0 5 s Off Trouble Pulses with amber 0 25 s On 1 75 s Off Flood Dete...

Page 10: ...ious conditions then these indicators provide fast estimation of current situation and defining action priority Table 16 describes performance of the indicators after alarms have been received Table 16 Performance of Single Color LEDs Partition Status LED Performance Fire 2 Alarm FIRE 2 Red Fire Alarm FIRE Red 0 25 s On 0 25 s Off Prealarm PREALARM Red 0 25 s On 1 75 s Off Intrusion Alarm Flood Al...

Page 11: ...0 8 s On 0 2 s Off Fire Alarm 0 6 s On 0 4 s Off Fire Prealarm 0 25 s twice 1 25 s Off Intrusion Alarm 0 25 s On 0 25 s Off Panic Alarm Panic Alarm Duress 0 25 s On 0 25 s Off Trouble 0 25 s On 1 75 s Off Access Request touching with an iButton Turns on for 0 25 s Access Denied Turns on for 1 s Access Granted Turns on for 0 25 s Others Off Table 19 Indication Mode Compatibility Indication Type Sup...

Page 12: ...ts are sent with time stamps determined by internal clock of the module All LEDs except for the power indicator turn off while the TROUBLE LED turns on Once per hour the module automatically synchronizes with the S2000M control panel 5 5 2 The module provides buffering event transmitted over RS 485 5 6 Network Address Network Address is meant to identify the module uniquely within an Orion integra...

Page 13: ...nstructions for transportation storage installation and usage 8 2 The average lifetime of the module is at least 10 years 8 3 Warranty period is 18 months since putting the module into operation but no more than 24 months from the manufacturer s date of issue 8 4 While submitting the module for repair please apply a report describing the failure 8 5 If you have any problems with programming or ope...

Page 14: ...rtificate РОСС RU ИК32 К00153 10 ACCEPTANCE AND PACKAGING CERTIFICATE Indicator Module S2000 BI S2000 BI Rev 02 Serial Number___________________ Is manufactured accepted in accordance with mandatory requirements of state standards and actual technical documentation packaged by CJSC NVP Bolid and approved as proper for operation Responsible for acceptance and packaging QCD _________________________...

Reviews: