3
2
MOUNTING AND WIRING THE MODULE
2.1
Mounting the Module
2.1.1
Mount the module in line with the Russian regulatory document
РД
.78.145-92 “Rules for Manufacturing and Commissioning. Fire and
Intrusion Alarm Installations”. Mount the module at a height above the floor
which is suitable to operate and maintain the device.
2.1.2
The module is to be mounted on walls or other constructions of
premises at places protected against atmospheric fallouts and mechanical
damage.
2.1.3
Prior to attaching the module, please ensure that the wall the module
is to be mounted to is solid, flat, and dry.
2.1.4
Mark points on the wall for four mounting holes in accordance with
Figure 1.
2.1.5
Drill the mounting holes. Then insert wall plugs into the holes and
screw two woodscrews provided in the two upper holes so that the distance
between a woodscrew head and the wall is about 7 mm.
2.1.6
Remove the right-side cover panel.
2.1.7
Hang the module on two woodscrews. Screw the remaining
woodscrew into the lower side mounting hole and fix the module on the wall.
Figure 2.
Opening
Cover Panel
2.2
Wiring the Module
2.2.1
Connect wires to the terminals as shown in Figure 3.
2.2.2
Please observe polarity while connecting the module to the power supply.
2.2.3
The cross section of wires should not exceed 1.5 sq. mm.
2.2.4
If the module, the control panel, or other Orion system devices connected to the RS-485
interface bus are supplied with power by different power supplies then couple their relevant “0V”
circuits.
2.2.5
Unless the module is the last or the first device in the RS-485 interface bus, remove the
EOL jumper from the module’s PCB (see Figure 3).
2.2.6
If necessary connect the external reader to the module as shown in Figure 3.
The module does not provide monitoring communication lines with the reader for good
conditions, so fire-fighting installations should not be operated by means of the reader connected to
the module.
2.2.7
Close the cover panel of the module (see Figure 2).
Figure 3.
External Connection Diagram
PS: Primary and (optionally) backup 10.2…28.4 V dc power supplies
+
S2000M Panel
Orion ISS
connection interface
S2000 Panel
+
Orion Pro
Software
+
To PS
+
iButton Reader
Buzzer
Tamper Switch
620
Ω
EOL Jumper
RS-485
LED R
LED GRN
0V
B
A
0V
ТМ