4
The purpose of this User’s Manual is to provide a basic understanding of principles and rules of
operation of MP 24/12V DC-DC Power Converter Module.
Only the personnel who have studied this manual are allowed to operation activities. All activities
on mounting, start-up, programming, and testing shall be performed in compliance with the
requirements of the regulatory documentation in force at the place of operation.
1
Description and Operation
1.1
Purpose
1.1.1
MP 24/12V DC-DC Power Converter Module (hereinafter referred to as the MP) is designed
to supply power to equipment of fire and intrusion alarm systems that require 12 V dc.
1.1.2
MP is intended for round-the-clock operation with specified output parameters when
cooperating with RIP-24 battery backed power supplies. The actual list of RIP-24 can be found at
http://bolid.ru/production/reserve/rip/
.
1.1.3
The design of the MP doesn’t imply operating it in ex-hazardous and flammable premises.
1.1.4
The MP provides protection against short circuit failures with recovering output voltage
automatically after repairing the failures.
1.1.5
The MP provides protection against reverse polarity of input voltage with further restoration
of performance.
1.2
Specifications
Table 1
No.
Parameter
Value
1.2.1
Input DC voltage range
20 through 30 V
1.2.2
Rated output voltage
(12.6
±
0.6) V
1.2.3
Load current
0.5
А
permanently
0.8
А
for a time up to 2 min
1.2.4
Current consumed by the module itself
8 mA max
1.2.5
Power consumed from the input power supply at maximum load
current
7 W max
1.2.6
Ripples of the output voltage (peak-to-peak) at rated load current 50 mV max
1.2.7
Enclosure protection degree as per GOST 14254-2015
IP20
1.2.8
Resistance to mechanical exposure as per OST 25 1099-83
Arrangement Category III
1.2.9
Vibration exposure:
- Frequency range
- Max acceleration
1-35 Hz;
0.5 g
1.2.10
Environmental category as per OST 25 1099-83
О
3
1.2.11
Operating temperature range
Minus 30 t50 °
С
1.2.12
Relative humidity
93 %
1.2.13
MP weight
0.1 kg
1.2.14
MP overall dimensions
55
×
38
×
20 mm
1.2.15
MTBF in the quiescent mode
40,000 hours
1.2.16
Survival probability
0.975 after 1,000 hours
1.2.17
Expected service life of MP
10 years
1.2.18
MP is ready to operate within one second upon input power supply turning on.