Bogart Engineering SC-2030 Technical Manual Download Page 5

1 of the TM-2030 INSTALLATION INSTRUCTIONS.

 

4.3 Tools and hardware required 

Drill with bits of suitable sizes for entry of telephone cable and/or Temperature sensor into SC-2030 plastic enclosure

 

Medium Phillips screwdriver for the large green terminal blocks connecting wire to panels and batteries.

 

Small Phillips screwdriver for four screws holding front plate enclosure

 

Wire cutters, wire strippers, and a lug crimper for the battery wire, the solar panel wire, etc.

 

SC-2030 charge controller

 

TM-2030 (TriMetric) battery monitor with sensing and power wires (assuming the TM-2030 will be connected)

 

If TM-2030 is not yet installed, it will require an electrical shunt: 500A/50mV or 100A/100mV size.  see TM-2030 

installation instructions.

 

Mounting hardware for the above, if required

 

Wire of suitable size and length (as determined in section 4.1.6) from panels to SC-2030 and SC-2030 to batteries

 

● 

Common four wire conductor “telephone cable” up to 100 ft. long—to go from SC-2030 to TM-2030. This is the common 4 

wire telephone extension cable with RJ11 connectors sold in different lengths at hardware or other stores in the telephone 
accessories section. The wiring must be crossed (crossover) between the two connectors, as shown in the lower right-hand 
corner of Figure 1. This is usually the way they are manufactured—but check.

 

Temperature sensor (optional but recommended unless batteries will remain at same temperature)

 

4.4 Installing the SC-2030, connecting solar panels, batteries, and Temperature sensor 

Plan to mount the SC-2030 in a well-ventilated and shaded area to prevent overheating, and protected from direct rainfall. The 
heat sink can get hot during charging; therefore, the charge controller must be installed beyond the reach of animals and young 
children.  The black heat sink fins should be vertical—not horizontal, which means the printing of "SOLAR" or "BATTERY" 
will be right side up or upside down (not sideways). 

 

4.4.1

 Run wires (size determined as described section 4.1.6) from solar panels to location for SC-2030, and from batteries to 

SC-2030 location with enough extra length to easily connect to large green terminal blocks. Carefully mark on the ends of the 
wire which are positive and which are negative—both to batteries and to solar panels.

 

4.4.2 

If communication (phone) cable has RJ14 connectors attached at both ends, check that connectors are "crossed" as shown 

in figure 1. Run phone cable from TM-2030 to SC-2030 location with sufficient length. If you have a RJ14 crimp tool and 
correct RJ14 connector, to avoid drilling a larger hole you could pass wire through a small drilled hole through TM-2030 
enclosure then use crimp tool to install connector (carefully observing polarity Fig 1). Don't yet connect the communication 
cable to the TM-2030 (unless connectors at each end are attached and you don't intend to put them on or change them later.)

 

4.4.3

 

Remove front panel and circuit board from SC-2030 enclosure by removing 4 screws and put it aside. Drill one or more 

holes in the SC-2030 enclosure to allow the communication cable and the temperature sensor wire (if used) to pass through in a 
location suitable to the positioning of the controller, wires and the rest of the system. The temperature sense connector requires 
a 5/16 diameter hole to pass through. For the communication cable, as described in 4.4.2 you could pass the wire through the 
hole and attach the connector similarly to 4.4.2 if you have the appropriate connector and crimping tool. Reminder: be sure the 
connectors are attached "crossed" as shown figure 1.

 

4.4.4 

Mount the enclosure on vertical surface so the heat sink fins go up and down. Use two screws on flanges, or you may drill 

your own holes internally and use those.

 

4.4.5 

Connect the temperature sensor connector (if used) and the communication cable to the two connectors on the back of the 

SC-2030 (inside the box). Place the circuit board back onto the enclosure board and secure with four screws.

 

4.4.6 

Place the temperature sensor (if used) near the batteries. The hole in the sensor could be connected to a battery terminal—

but this is not necessary for it to measure temperature.

 

       

For safety, turn off power from batteries and solar panels before doing next step

 

4.4.7 

Connect the wires from batteries and the solar panel wires to the controller.

 

For the following steps, refer to wiring 

diagram, Figure 1. For safety, turn all switches and circuit breakers off while making the connections. While 
voltages in a 12V or 24V solar system are generally considered safe from electrical shock, amperages can be 
very high and can create powerful arcs if accidentally shorted, or when connections are made or unmade.

 

a. Connect the SC-2030 minus wire to the batteries. Observe in figure 1 how the SHUNT is connected to the 
batteries.  The shunt has two large bolt terminals. One is connected to the battery negative terminal—the 
other side is connected to the loads in your system.  The wire from the SC-2030 “BATTERY minus” terminal 
(large green) must go to the LOAD side of the shunt.  Avoid a common mistake of connecting this directly to 
the negative post of the battery. If you make this mistake the solar current will not register as “amps” on your 

Summary of Contents for SC-2030

Page 1: ...to better preserve the capacity of your battery system 1 Amp hour counting Many battery companies recommend that when batteries are recharged they should be overcharged so that 104 to 120 percent of the charge that was previously removed should be replaced before going into float Most controllers don t measure this When connected with the TriMetric this controller measures the amp hours used and a...

Page 2: ...r full efficiency May be safely used with panels up to 45A however charging current will be reduced to protect charger MINIMUM in out power efficiency at 30A 97 5 12V systems 98 5 24 V systems MINIMUM in out power efficiency at 15A 99 Battery capacity 10 to 10 000 amp hours Terminal block wire gauge Up to 6 AWG Larger stranded cables you can remove some strands to fit Charging profiles Three stage...

Page 3: ...GM or liquid electrolyte These determine the charging only when the TM 2030 is not connected otherwise they are ignored In this case there is an absorb stage set to 14 6 or 29 2 volts for 12 or 24V liquid electrolyte systems or 14 3 or 28 6 for AGM systems which runs for two hours followed by a float stage of 13 2 or 26 4 volts 4 1 3 Temperature Compensation The optional temperature sensor is reco...

Page 4: ...s Check volts For accurate battery voltage control the TriMetric s voltage measurement wire called B1 in TriMetric wiring diagram must be connected directly or close to the battery s positive terminal Check amps on the AMPS TriMetric display Under zero current conditions when all loads and charging sources are off the TriMetric s ampere indicator must show 0 0A or 0 1A at most when using the stand...

Page 5: ...tool and correct RJ14 connector to avoid drilling a larger hole you could pass wire through a small drilled hole through TM 2030 enclosure then use crimp tool to install connector carefully observing polarity Fig 1 Don t yet connect the communication cable to the TM 2030 unless connectors at each end are attached and you don t intend to put them on or change them later 4 4 3 Remove front panel and...

Page 6: ...t the absorb voltage Flashing 3 times indicates floating mode Flashing 4 times in higher voltage finish limited current charging With TM 2030 connected only Flashing 5 times at maximum voltage finish limited current charging With TM 2030 connected only Flashing 6 times Was in float now discharging but still at least 98 full With TM 2030 connected only Flashing zero times Discharging and less than ...

Page 7: ...t shown on the front panel called UPr Unused power which displays this If most of the solar power is now surplus because the batteries are getting well charged YES will show on the display If a lesser amount the display will indicate the approximate number of watts that are being wasted Refer to the Quick Reference Guide section 2 1 Also listed there is information about observing solar amps SOL a...

Page 8: ...energy electrons into the battery The battery always tends to resist the tendency to push the electrons in the voltage of the charger must be high enough to overcome the resisting force of the battery This is a little like pushing water into a pipe which is under pressure enough force must be provided to push it in or it will not go The current or amperes is a measure of how much charge energy is ...

Page 9: ...e variations on this method 1 Charge above the gassing voltage until the amperes drop to a sufficiently low value say an ampere value that is 1 or 0 5 of the amp hour capacity of the batteries 2 Charge until the value of amps into the batteries stops decreasing for a specified period of time and stays at this constant value for perhaps a couple of hours 3 Charge until the charger has replaced a sp...

Page 10: ...r current until it reaches the limiting absorb voltage shown After that it charges for an absorb time of two hours Then it regulates at the float voltage shown 6 4 Two Graphs of charging profiles for SC 2030 when TM 2030 is connected The first profile figure 2 is more typical of most good solar chargers However the SC 2030 has an additional unusual option of setting a percentage of overcharge valu...

Page 11: ...rops below P2 P3 AND overcharge P20 OR Timer expires with P14 time For the 4 state profile Timer starts counting with P14 time as shown on 4 state charging profile The first time after the charger is turned on Goes into float when Amps drops below P2 P3 OR Timer expires After the first time Amps drops below P2 P3 at least once during Absorb AND overcharge P20 OR Timer expires with P14 time 6 6 Bat...

Page 12: ...r repaired at Bogart Engineering s discretion provided it has not been subjected to abuse or misapplication For warranty service please email bogart bogartengineering com A return merchandise authorization is required for all merchandise to be returned to Bogart Engineering How to obtain customer service Please review our support page before attempting to contact us Our distributors are able to an...

Page 13: ...es compared to the most recent discharge before going into float Also it has been considered best suited for AGM or Gel type lead acid batteries however recently some manufacturers are recommending the four stage profile next page for AGM type batteries Liquid electrolyte batteries can usually benefit from four state solar charging Figure3 To select three stage charge control set program P21 finis...

Page 14: ...Max over voltage time allowed 0 1 10 0 hours Absorb stage terminates when Charged setpoint amps When P21 not OFF Max finish volts P15 value When P21 is OFF Max finish volts P1 value 4 state charging profile for liquid electrolyte batteries Figure 3 Bulk Absorb Finish Absorb Float Time counting P14 starts here when P21 is not off Starts here when P21 is off Time counting temporarily stops whenever ...

Page 15: ...tery systems Up to 30 amps of panels can be used If more than 30 amps is used the SC 2030 will safely limit current 1 A FUSE Optional battery temperature sensor Small wires go to connector in SC 2030 SHUNT Choose 500A 50 mV or 100A 100mV TWO KELVIN SCREWS 4 small wires from battery to meter up to 100 feet Usually a cable with four 22 or 24 wires is used Optional connection for measuring voltage on...

Page 16: ...les previously connected to the battery negative pole must then be reconnected to the load side of the shunt Connect four wires from shunt and battery to Meter Cable consisting of small wires 22 up to 100 feet long need to connect from the TriMetric to the shunt and batteries WHAT S INVOLVED IN INSTALLING THE BOGART ENGINEERING SC 2030 Solar Charger Brief description Complete description is in the...

Reviews: