BACKUP NANO INVERTER AND AC BALLAST/DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.

• Connect the two BLUE Unit Enable wires together once all other connections have been made to enable the unit.
• Apply AC power to enter charging mode.
• Remove AC power to enter emergency mode.                                                                                                    
• For incandescent or non-dimming loads no greater than 10 VA, cap off all unused dimming (DIM) leads separately.
                                                                                                                                                                  
2  These connections have been evaluated to comply with requirements for UL1310 Class 2 Power Units.

WIRING DIAGRAM

DRIVER

    Or

BALLAST

DIM+ OUT (VIOLET/PINK)

 

DIM- OUT (GRAY/PINK

)

NEUTRAL OUT (RED/WHITE)

HOT OUT (RED/BLACK)

ELI-S-10

DIM+ IN (VIOLET)

DIM- IN (GRAY)

NEUTRAL IN (WHITE)

Unswitched HOT (RED)

Switched HOT IN (BLACK)

(BROWN/WHITE)

 

Unit Enable (BLUE)

(VIOLET/WHITE)

 

Unit Enable (BLUE)

Earth Ground

2

2

2

BROWN

VIOLET

 

  LIGHT

SOURCE

(use grounding kit provided with unit)

• •

Summary of Contents for ELI-S-10

Page 1: ...l and auxiliary power supplies and inverter connector of the backup nano inverter before servicing 4 This backup nano inverter is for factory or field installation 5 An AC power source 120 or 277 VAC 60 Hz ahead of any wall switch is required to provide battery charging current 6 Do not install near gas or electric heaters 7 This product is for use in indoor or damp locations where the ambient tem...

Page 2: ...f the AC ballast driver See Illustration 1 for typical installation and select appropriate mounting method STEP 1 DISCONNECT AC POWER FROM FIXTURE INSTALLATION 2 This product is suitable for field installation with suitable luminaires including LED fluorescent and incandescent luminaires with 0 10V dimming capability The 0 10V dimming capability may not be necessary for luminaires that operate und...

Page 3: ...r has been charging for 1 hour Charge for 24 hours before conducting a long term discharge test Refer to OPERATION During normal operation AC power is supplied to the AC ballast driver through the backup nano inverter and the inverter charges its internal battery Connecting the blue connector wires enables the emergency circuit and supplies power to the control monitor circuit The backup nano inve...

Page 4: ...escent or non dimming loads no greater than 10 VA cap off all unused dimming DIM leads separately 2 These connections have been evaluated to comply with requirements for UL1310 Class 2 Power Units WIRING DIAGRAM DRIVER Or BALLAST DIM OUT VIOLET PINK DIM OUT GRAY PINK NEUTRAL OUT RED WHITE HOT OUT RED BLACK ELI S 10 DIM IN VIOLET DIM IN GRAY NEUTRAL IN WHITE Unswitched HOT RED Switched HOT IN BLACK...

Reviews: