>  The backup nano inverter will be located between the AC power sources and the AC ballast/driver as shown in  

wiring diagram section of instructions.

>  NOTE: The backup nano inverter may be installed in close proximity to the fixture or remote from the fixture. 

The maximum remote distance using 16 AWG wire is 100 ft. Contact the factory for more information.

>  The AC ballast/driver receives power from the backup nano inverter. Identify the output wires of the backup 

nano inverter by the presence of the red/black and red/white leads.

NOTE:  Make sure that the necessary branch circuit wiring is available. An unswitched 

source of power is required. The unswitched and switched power source must be fed 
from the same branch circuit.

WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON THE RED/BLACK AND 

RED/WHITE OUTPUT LEADS PRIOR TO INSTALLATION, BLUE CONNECTOR MUST BE OPEN. 

JOIN BLUE UNIT ENABLE WIRES AFTER INSTALLATION IS COMPLETE AND AC POWER IS 

SUPPLIED.

INSTALLING THE BACKUP NANO INVERTER

>  Disconnect all power sources to the lighting fixture and ensure they are locked out during installation or  

maintenance.

>  The AC ballast/driver must be sourced from the backup nano inverter.

>  Select a suitable location for the backup nano inverter and install such that its output leads can connect to 

the input leads of the AC ballast/driver.  

>  See Illustration 1, for typical installation and select appropriate mounting method.

STEP #1 

DISCONNECT AC POWER FROM FIXTURE

INSTALLATION

2

  This product is suitable for field installation with suitable luminaires including LED, fluorescent, and incandescent luminaires 

with 0-10V dimming capability.  The 0-10V dimming capability may not be necessary for luminaires that operate under 10VA. 
This product has been designed to reliably interface with a wide selection of luminaires which are electrically compatible 
with 120 or 277 VAC at 60Hz and a 0-10V dimming interface. However, compatibility cannot be guaranteed with all current 
and future luminaire systems. 

  Compatibility testing of the end-use system is recommended. Please contact the factory with any questions.  After installa-

tion, it will be necessary to measure the egress lighting illumination levels to ensure it complies with national, state, and 
local code requirements.

NOTE: Considerations must be made to protect the wires of the ELI-S-10 if installed outside of the luminaire.

   If the application requires the ELI-S-10 to be mounted on 

top of the luminare please use Model ELI-S-10C instead or 

wire bundle cover kit (RMC-60). Please note, the RMC-60 kit 

contains enough parts to install two products.

Nano

Inverter

ILLUSTRATION 1

>  Verify that the blue connector is disconnected. Note that the unswitched hot connects to the red input lead 

of the backup nano inverter.

STEP #2

CONNECT THE BACKUP NANO INVERTER TO THE PROPER LINE VOLTAGE

Summary of Contents for ELI-S-10

Page 1: ...l and auxiliary power supplies and inverter connector of the backup nano inverter before servicing 4 This backup nano inverter is for factory or field installation 5 An AC power source 120 or 277 VAC 60 Hz ahead of any wall switch is required to provide battery charging current 6 Do not install near gas or electric heaters 7 This product is for use in indoor or damp locations where the ambient tem...

Page 2: ...f the AC ballast driver See Illustration 1 for typical installation and select appropriate mounting method STEP 1 DISCONNECT AC POWER FROM FIXTURE INSTALLATION 2 This product is suitable for field installation with suitable luminaires including LED fluorescent and incandescent luminaires with 0 10V dimming capability The 0 10V dimming capability may not be necessary for luminaires that operate und...

Page 3: ...r has been charging for 1 hour Charge for 24 hours before conducting a long term discharge test Refer to OPERATION During normal operation AC power is supplied to the AC ballast driver through the backup nano inverter and the inverter charges its internal battery Connecting the blue connector wires enables the emergency circuit and supplies power to the control monitor circuit The backup nano inve...

Page 4: ...escent or non dimming loads no greater than 10 VA cap off all unused dimming DIM leads separately 2 These connections have been evaluated to comply with requirements for UL1310 Class 2 Power Units WIRING DIAGRAM DRIVER Or BALLAST DIM OUT VIOLET PINK DIM OUT GRAY PINK NEUTRAL OUT RED WHITE HOT OUT RED BLACK ELI S 10 DIM IN VIOLET DIM IN GRAY NEUTRAL IN WHITE Unswitched HOT RED Switched HOT IN BLACK...

Reviews: