3. MOUNTING INSTALLATION 

 

CEILING MOUNTING 

The heater is intended for installation in a suspended ceiling mounted within or on the 'tee' bar supports. For optimum results do not fit in ceilings 
higher than 3m. As air is only introduced through the front of the unit the heater may be sighted anywhere. The air intake and discharge areas must 
be kept completely clear for a minimum of 1.5m from the front of the heater. In an area using multiple units, heaters should be spread to provide an 
even heat distribution. 

 

IMPORTANT! 

A minimum clearance of 200mm is required above the ceiling grid and the original roof/ceiling to allow installation of this heater. 

 

IMPORTANT! 

DO NOT use plastic type diffusers as these may be damaged by the heat. 

 

IMPORTANT!

 Ensure that  the mounting  surface  /  ceiling supports are  capable of  taking  the  additional  weight  of the  heater there  are 2  eye 

hooks supplied with the heater that should be used if additional support of the heater is required. 
When using the diffuser, the four Z brackets provided must be attached to the side of the heater to enable the heater to be supported by the 'tee' bar 
and immediately above the diffuser. 

4.  ELECTRICAL CONNECTIONS 

230V SINGLE PHASE 

– Power Connection 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing. 
Drawings show connections inside the black terminal box on the outside of the heater. 

Do NOT use power tools to undo or do up terminal screws in the Power Supply Box. 

Please Note: - Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 

 

 
Standard Connection 
 
Use 2.5mm² 3 Core Mains Cable (see note above). 
Connect Brown wire 

– Terminal 1 or L. 

Connect Blue wire 

– Terminal 5 or N. 

Connect Green / Yellow wire 

– Terminal E or 

 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY 
THE GUARANTEE 
 
 

Once  the  mains  cable  has  been  connected  the  heater  will 

not  work  until  a  suitable  controller  is  attached 

to  the 

heater using a CAT5 network cable. We recommend you use our cables as they have been tested for compatibility 
between all the controllers and the various different heater models. Instructions on connecting controllers is found 
within the controller packaging.  

 

 

 

5. MAINTENANCE

 

Note:

 Before examining or carrying out any maintenance ensure the heater has cooled down and is disconnected from the mains supply. 

The heaters are intended to operate for many years, problem free. All moving parts are factory lubricated and therefore should require no service. 
Maintenance is limited to keeping both the inlet and outlet areas free from any accumulation of dust or any other foreign materials. This is especially 
important immediately before the heating season. Any dust build up can be loosened using a brush and a vacuum cleaner applied to the airways to 
ensure  completed  removal  of  any  dust.  When  the  heater  is  first  turned  on  after  cleaning  an  unusual  odour  may  be  noted  this  is  due  to  the  dust 
particles which inevitably will be disturbed and will be burnt off from the heating element. 

If in any doubt always consult a qualified electrician for advice. 

 

 

6. AUTO CUT OUT

 

 

This heater is fitted with a semi-automatic safety device to prevent overheating.  The device will isolate the heating element while the fan continues 
to operate. Should this occur,  disconnect the heater from the mains supply for a minimum of 5 minutes,  check and remove any foreign materials 
around the airways. If the heater fails to operate or the safety cut out operates again, turn off the heater and contact a qualified electrician. 

 
 

NOTE: It is our policy to continually improve products and as such we reserve the right to alter data, specifications and component parts without 

prior notice. 

 

IMPORTANT: 

No liability is accepted for incorrect use of this product.

 

WARRANTY: 

Your  BN  Thermic  product  is  guaranteed  for  one  year  from  date  of  purchase.  We  will 

repair  or  replace  at  our  discretion  any  part  found  to  be  defective.  We  cannot  assume  any 
consequential  liability.  This  guarantee  in  no  way  prejudices  your  rights  under  common  law  and  is 
offered as an addition to consumer liability rights. 

REGISTER:

 Activate your warranty by registering online at www.bnthermic.co.uk and retain this 

installation data for future reference. 

 

 

 

 

 

 

 

 

 

 

XC-45INS-v01-1 

This product conforms to EU Directive 2002/96/EC. 
This appliance bears the symbol of the crossed waste bin. This indicates that, at the end of its useful life, it must not be disposed of as 
domestic  waste,  but  must  be  taken  to  a  collection  centre  for  waste  electrical  and  electronic  equipment.  It  is  the  user's  responsibility  to 
dispose  of  this  appliance  through  the  appropriate  channels.  Failure  to  do  so  may  incur  penalties  established  by  laws  governing  waste 
disposal.

 

BN Thermic Ltd,  

34 Stephenson Way, 

 Crawley, RH10 1TN 

Tel: +44 (0) 1293 547361 

Email: [email protected] 

Web: www.bnthermic.co.uk 

 

Reviews: