G U R A T I O N .  

 

4 .   C O N F I G U R A T I O N .  

 

1. Ensure the metal link is present in the small green terminal block marked J2. 

2.Select which temperature range you require by using switch No 1. 

ON = 0ºC to 20ºC and uses the white rotary knob to set the temperature.  

OFF = 10ºC to 30ºC and uses the black rotary knob to set the temperature.  

3. Decide if you require window opening (see section 7) 

4. Fit cover securely using all 4 corner screws. 

When the power is turned on, the thermostat will start to turn the heating ON / 
OFF maintaining temperature set point. 

NOTE:- 

Switch’s  3 - 6 are disabled and have no function.

 

 

5 .   U S I N G   W I T H   A   R E M O T E   V O L T - F R E E   T I M E R   O R   B M S .  

 
The time switch takes over controlling when the thermostat operates.  

 

1. Remove the metal link in the small green terminal block marked J2. 

2. Connect the PROTIM-7 so that one wire runs between S-in to one of the green J2 
terminal  blocks and  another  wire  between  S-out  and the  other  J2  green  terminal  as 
shown in picture above. DO NOT CONNECT THESE 2 WIRES TO A 240V SUPPLY. 

Please  note  there  is  only  5V  DC  present  so  doorbell  wire  can  be  used  to  connect 
between the controllers. 

3. Wire PROTIM-7 to suitable fused supply as per timer

’s instructions. 

 

BMS 

– Building management system 

The  controller  can  also  be  connected  to  a  zero-volt  relay  controlled  by  a  building 
management system. When the relay is open thermostat is OFF, when relay is closed 
thermostat turns ON. 

 

 

Optional PROTIM-7 

7 Day Time Switch 

Back view of the 
PROTIM-7 timer 