Transport
Version 1.1
Page 46 of 113
Storage conditions:
Closed and dry room with a room temperature from +10 °C to +30 °C (temperatures
below and above this range shorten the service life)
Relative air humidity must be a maximum of 80% (non-condensing).
The spatial distance from walls or other objects must be at least 50 cm.
The battery storage system must be stored only in an upright position.
Never clean the battery storage system or its immediate vicinity using a vapour jet or spray water.
Dirt and water may enter the battery storage system and cause major damage.
Before storing the lithium ion battery, inform your insurer.
After a storage time of a maximum of 6 months, execute an equalisation charge process for the battery as
described in the operating manual of the battery inverter.
-
If this is not done, batteries may get damaged.
-
If this is not done, it will lead to consequential costs which will not be borne by BMZ.
The entire time of storage of batteries must be included in the usage duration.