6.7. RVC and Ripple control
The RVC threshold (or thresholds) and the RVC hysteresis are both set by the user according to the use.
Mains signaling voltage, called “ripple control signal” in certain applications, is a burst of signals, often applied at a
non-harmonic frequency, that remotely control industrial equipment, revenue meters, and other devices.
Parameter
Description
Factory setting
Setting range
RVC threshold
The RVC threshold is a percentage of Udin
3,3%
1 ... 100%
RVC hysteresis
The RVC hysteresis is a smaller percentage of Udin
1%
1 ... 20%
Ripple -control
Adjustable by PMS
50 Hz
50 Hz ... 3 kHz
According to the norm the ideal settings is RVC threshold on 3,5% of Udin and hysteresis on 1% of Udin.