24
Mains Fusing
The AC mains input is protected by an internal fuse of quick acting, high breaking
capacity type and rated at 250V 10A.
Low Voltage Disconnect Modes
Low Voltage Disconnect (LVD) is a feature of
BatteryPlus35
that protects the battery
from deep discharge preventing battery health deterioration. The are two LVD modes
of protection for the battery, Eco mode and Storage mode.
ECO Mode
If the battery voltage drops below the ECO mode threshold, then the load outputs L2
to L14 are turned off, while L1 is left on. The communication bus and the accessories
connected to this bus are left on.
If no sources are available, a temporary recovery can be done by cycling the remote
Isolation switch on the
BatteryPlus35
or pressing the battery button on the
Trek
, this
will turn on all the loads for short time.
In this mode, a full recovery can only be done if the Battery voltage rises above the
recovery threshold or if any power source is available, all outputs will be turned back
on.
Storage Mode
If the battery discharges further and its voltage drops below the storage mode
threshold, output L1 to L14 are all turned off. In this state any accessory connected
to the communication bus is also turned off.
In storage mode the battery current drain is less than 15mA.
If no sources are available, a temporary recovery can be done by cycling the remote
Isolation switch on the
BatteryPlus35
. All loads will be turned on for short time.
In this mode, a full recovery can only be done if a power source is available and the
battery voltage rises above the recovery threshold.
Table 3:
ECO and storage mode thresholds
Lead Acid
LiFePO4
ECO mode threshold
10.5V
12.0V
Storage mode threshold
9.8V
11.5V
Recovery threshold
12.8V
13.8V
ECO And Storage Mode Thresholds