BMC ECON-DB-2 Installation Instructions Manual Download Page 17

Manual 2100-702D 
Page 

17 of 29

TABLE 5

Checkout Menu Levels

TABLE 4

Setpoints Menu Levels

Menu Level

Default 

Value

Range

Notes

MAT
SET

53°F

38°F to 
65°F

Mixed Air Temperature setpoint 
at which the economizer 
damper will begin to modulate 
to maintain setting

LOW T
LOCK

0°F

-45°F to 
80°F

Low outdoor ambient 
temperature for compressor 
lockout

DRYBLB
SET

60°F

48°F to 
80°F

Maximum outdoor 
temperature setting for “free” 
economizer cooling

ENTH
CURVE

ES3

ES1,
ES2,
ES3,
ES4 or
ES5

Enthalpy boundary “curves” 
for economizers using temp/
humidity sensor, see “Enthalpy 
Settings” explanation

MIN
POS

2V

2 to 10 
VDC

Actuator voltage for Minimum 
Position – see 

Minimum 

Position Note

EXH1

50%

0 to 
100%

Setpoint for damper if exhaust 
fan is powered by economizer

EXH2

6%

0 to 
100%

Setpoint for AUX output signal

DCV SET
(See 

NOTE

 

under Table 
7 on page 
18)

1100

500 to 
2000

Displays only if a CO

2

 sensor 

is connected. Setpoint for 
Demand Control Ventilation 
of space. Above the setpoint, 
the OA dampers will modulate 
open to bring in additional OA 
to maintain a space ppm level 
below the setpoint.

NOTE: CHECKOUT

 functions bypass the normal 

5-minute delay for compressor protection. Be sure to 
allow for enough time to pass between tests so the 
compressor is not damaged from extreme short-cycling.

MINIMUM POSITION NOTE:  

Minimum position 

setting has been preset to 10V which when connected 
to MC4002 Lead/Lag Controller System will allow 
economizer to drive wide open per emergency ventilation 
strategy as detailed in MC4002 Instructions. This may 
require resetting to a lower value per job specifications.

4. 

CHECKOUT:

 from the main screen, press the 

SCROLL (UP/DOWN) BUTTONS

 to navigate through the 

six (6) basic menu items to the 

CHECKOUT

 menu.

  –  Push the 

SELECT (ENTER) BUTTON

 to choose the 

CHECKOUT

 menu.

  –  Navigate through the multiple levels of 

CHECKOUT

 

by pushing the 

SCROLL (UP/DOWN) BUTTONS

.

  –  To perform a specific test in the 

CHECKOUT

 menu, 

press the 

SELECT (ENTER) BUTTON

 to choose a 

particular exercise, 

“RUN?

” 

will appear. Press the 

SELECT (ENTER) BUTTON

 again to activate this 

exercise. After a short pause, 

“IN PROGRESS”

 

will 

appear as the test activates. 

“DONE” 

will display 

after the test is complete. Press the 

MENU UP 

(EXIT) BUTTON 

to end the test and/or turn off the 

activated relay.

  –  For specific 

CHECKOUT

 level information, refer to 

Table 5

.

NOTE:

 Economizer assembly should be ready to 

put into service. At any point during operation, in 
economizer mode or idle, real-time information from 
sensors and integral components can be accessed from 
the 

STATUS

 menu.

5. 

STATUS:

 from the main screen, press the 

SCROLL 

(UP/DOWN) BUTTONS

 to navigate through the six (6) 

basic menu items to the 

STATUS

 menu.

  –  Push the 

SELECT (ENTER) BUTTON

 to choose the 

STATUS

 menu.

  –  Navigate through the multiple levels of 

STATUS

 

by 

pushing the 

SCROLL (UP/DOWN) BUTTONS

.

 

–  As the 

STATUS

 menu simply gives input/output 

information in real-time, there is no way to 
change or otherwise alter the displayed criteria.  
It is simply a window into the operation of the 
economizer controller.

  –  For specific 

STATUS

 level information, refer to 

Table 6 

on page 18.

NOTE:

 Upon power-up (or after power failure or low 

voltage condition), the controller will begin a 5-minute 
time delay before enabling mechanical cooling.

Menu Level

Notes

DAMPER VMIN-HS

Positions damper to the minimum amount 
of opening allowed by actuator

DAMPER VMAX-HS

Opens damper to the MIN POS level 
indicated in the 

SETPOINTS

 menu. See 

Minimum Position Note 

above.

DAMPER OPEN

Forces damper to full open position, energizes 
exhaust contacts

DAMPER CLOSE

Positions damper to completely closed 
position

CONNECT Y1-O

Forces Y1-OUTPUT to compressor

CONNECT Y2-O

Forces Y2-OUTPUT to compressor

CONNECT EXH1

Setpoint for damper if exhaust fan is 
powered by economizer

CONNECT EXH2

Setpoint for AUX output signal

CONNECT AUX

Depending upon AUX OUT setting from 

SYSTEM SETUP

 menu:

NONE – no action
ERV – 24VAC out for ERV & NOT 
Economizer
SYS – 24VAC out for alarm

Summary of Contents for ECON-DB-2

Page 1: ...ions are written to cover field installed economizers but are also includedwithfactory installedeconomizers Forfactory installedeconomizers all portions addressing installation are for reference only...

Page 2: ...th Economizer 14 Figure 13 JADETM Economizer Controller 15 Figure 14 100 Outside Airflow Path 20 Figure 15 Mixed Airflow Path 20 Figure 16 100 Closed Loop Airflow Path 19 Figure 17 CO2 Sensor Default...

Page 3: ...ent Concealed damage not discovered until after loading must be reported to the carrier within 15 days of its receipt Description ECON DB and ECON WD economizers are designed to be used with the wall...

Page 4: ...panel and screws save Ventilation access panel discard Filter access panel discard Filter save Outer and inner control panel doors and screws save 4 Remove and discard the exhaust cover plate save sc...

Page 5: ...ANEL PANEL DISCARDED THIS PANEL IS ACCESS DOOR CIRCUIT BREAKER FILTER ACCESS FILTER BRACKETS INNER CONTROL PANEL DOOR CONDENSER EXHAUST PLATE DISCARD AND SAVE SCREWS MIS 3620 SHOWN FACING DOWN PARTITI...

Page 6: ...RE 3 Filter and Filter Brackets REFERENCE ANGLE 30 30 REFERENCE ANGLE BRACKET LEFT FILTER THERMISTOR BRACKET FILTER RIGHT FILTER LOCATION MOUNTING HOLE LOCATED BEHIND THE C BREAKER OFFSET PLATE FOR TH...

Page 7: ...acket Fill Plate Installation LEFT HAND VENT RIGHT HAND VENT BRACKET LONG FILTER 4 REGULAR SCREWS BRACKET LONG FILTER BRACKET SHORT FILTER 4 REGULAR SCREWS MIS 3814 LEFT HAND UNIT RIGHT HAND UNIT INST...

Page 8: ...ies provided to the other wires in the grommet Ensure the wire harness cannot contact moving parts or copper tubing Replace side grilles Economizer Installation 1 Connect 12 pin male plug into female...

Page 9: ...the shield to aid in mounting the sensor replace after mounting sensor Insert white two pin sensor plug into sensor housing Coil excess orange wires and wire tie to suction discharge line FIGURE 7 Mi...

Page 10: ...immediate start up is not desired continue with the basic installation process by skipping to Step 4 The air hood assembly can be partially disassembled at a later time for start up checkout procedure...

Page 11: ...occupied periods Must be configured for multi stage for Y1 output to be active 1st stage cooling For dehumidification must be configured for No Economizer for YO D to be active for humidity control 4...

Page 12: ...signal for modulating ventilation 3 6 8 2 dehumidification must be configured for No Economizer for YO D to be active for humidity periods Must be configured for multi stage for Y1 output to be active...

Page 13: ...ot add these wires if setting up for modulating control See note 6 7 Jumper needs added 8 For 8403 058 change system type set up Function 1 From 5 2 Heat 1 Cool heat Pump to 6 2 Heat 2 Cool Convention...

Page 14: ...if setting up for modulating control See note 6 7 Jumper needs added 8 For 8403 058 change system type set up Function 1 From 5 2 Heat 1 Cool heat Pump to 6 2 Heat 2 Cool Conventional For 8403 059 No...

Page 15: ...NTS customizable operational parameters 3 SYSTEM SETUP customizable application programming see Revew Customize System Setup 4 ADVANCED SETUP further application and operational options 5 CHECKOUT ins...

Page 16: ...quipment in order to have correct operating sequences for the economizers DO NOT change to CONV A C setting just because the equipment is an air conditioner and not a heat pump 2 ADVANCED SETUP from t...

Page 17: ...S To perform a specific test in the CHECKOUT menu press the SELECT ENTER BUTTON to choose a particular exercise RUN will appear Press the SELECT ENTER BUTTON again to activate this exercise After a sh...

Page 18: ...g for mechanical compressor cooling 24V on Y1 O COOL Y2 IN ON OFF Indicates if 24V signal is being received on terminal Y2 I COOL Y2 OUT ON OFF Displays if controller is actively calling for Stg 2 coo...

Page 19: ...lable enthalpy boundaries are all subject to specific OA temperature OA humidity and OA dew points If all of the OA conditions are below the specific points outlined in each boundary the conditions ar...

Page 20: ...long as the OA conditions do not drop below the preset DRYBULB SET ENTH CURVE settings in the SETPOINTS menu see Figure 15 3rd Stage Cooling if available closes and sends a signal to JADE control whic...

Page 21: ...Manual 2100 702D Page 21 of 29 FIGURE 16 100 Closed Loop Airflow Path CONDENSERAIR AIRFILTER 100 RETURNAIR COOLINGCOIL SUPPLYAIR DAMPERBLADE ELIMINATOR MIST CONDENSERCOIL MIS 3614...

Page 22: ...COOLING REQ D MECHANICAL COOLING BEGINS ECON DAMPER CLOSED OR MIN POSITION CONDITIONED SPACE LOAD IS PICKED UP BY MECHANICAL COOLING THERMOSTAT IS SATISFIED AND SYSTEM SHUTS DOWN CONDITIONED SPACE LO...

Page 23: ...nce Climate fan speed simultaneously If the outdoor conditions are not acceptable the Y2 terminal will energize full load compressor and increase the fan speed to the rated airflow When the temperatur...

Page 24: ...AND MECHANICAL COOL THERMOSTAT CALLS FOR 2ND STAGE COOLING BRINGS IN RATED INDOOR FAN SPEED IS ADDITIONAL COOLING REQ D THERMOSTAT IS SATISFIED AND SYSTEM SHUTS DOWN THERMOSTAT CONTROL CALLS FOR 1ST...

Page 25: ...ER CONFIGURATION MODE USE ARROWS TO SELECT SETTING PUSH MIDDLE BUTTON TO CHANGE CONTROLLER WILL SHOW SET MIS 4025 Settings Recommended Default RON Not Used ROF Not Used DSP C CT UNI US US COL 700 0 CO...

Page 26: ...Manual 2100 702D Page 26 of 29 GRAPH 1 W J18 Ventilation Delivery GRAPH 2 W J24 Ventilation Delivery...

Page 27: ...Manual 2100 702D Page 27 of 29 GRAPH 3 W J30 Ventilation Delivery GRAPH 4 W J36 Ventilation Delivery...

Page 28: ...NPUT 2ND STAGE COOLING OUTPUT MALE RELAY BLACK WHITE PLUG PLUG 7 PLUG 12 PIN PLUG 0 10 VDC CO2 CONTROL INPUT 12 PIN PLUG PLUG MAT MAT OAT OAT S BUS Y2 O Y1 I EXH1 AUX1 O Y1 O C R S BUS Y2 I ACT 24V BL...

Page 29: ...OCC AUX2 I Y2 I ACT 24V BLACK WHITE 12 5 6 3 2 8 9 BLACK 11 3 BLACK ACT ACT IAQ24V IAQ IAQ DAMPER MOTOR 1 2 3 4 7 11 3 FEMALE 12 PIN PLUG 1 7 MALE 12 PIN PLUG NO NC COM MALE 1 2 3 4 5 6 6 5 4 3 2 1 5...

Reviews: