Manual 2100-702D
Page
16 of 29
TABLE 2
System Setup Menu Levels
TABLE 3
Advanced Setup Menu Levels
Menu Level
Default
Value
Range
Notes
INSTALL
01/01/10
Display Order = MM/DD/YY
Setting Order = DD/MM/YY
UNITS DEG
°F
°F / °C
Sets controller to read in
either measurements
EQUIPMENT HP(B)
HP
Heat Pump HP
CONV = A/C
AUX IN
HP(B)
HP(O)
HP(B
Energize on Cool
Energize on Heat
FAN SPEED
1 Speed
1 Speed
2 Speed
FAN CFM
5000
100 to
15000
Not applicable
AUX OUT
EXH2
NONE
ERV
EXH2
SYS
Product can be used to
signal other devices
OCC
INPUT
INPUT or
ALWAYS
INPUT is for dedicated OCC
signal, ALWAYS is for all
other situations
FACTORY
DEFAULT
NO
YES or
NO
Resets to factory defaults if
changed to YES
Menu Level
Default
Value
Range
Notes
MA
LOW
SET
45°F
35-55°
Temp to activate freeze
protection — Close Damper
FREEZE
POS
CLO
CLO or
MIN
Damper position upon freeze
protection
STG3
DLY
15 MIN
0 to 4.0h
or OFF
Delay for 3rd Stage Cooling –
allows for 3 stages of cooling,
one stage for econ & two
stages for compressor
DMPR
POS
CLO
CLO or
OPN
Where damper goes upon
shutdown signal
MA T
CAL
0.0°F
+/-2.5°F
from
actual
reading
Mixed Air Sensor temperature
calibration
OA T
CAL
0.0°F
+/-2.5°F
from
actual
reading
Outdoor Air Sensor
temperature calibration
OAS H
CAL
0%
+/-10%
from
actual
reading
Outdoor Air Humidity Sensor
calibration for economizers
using temp/humidity sensor
* In
SYS SETUP, the correct Equipment setting is HP
and for the AUX2 IN is HP (B) in all applications.
This is correct for both air conditioner and heat
pump equipment in order to have correct operating
sequences for the economizers. DO NOT change to
CONV = A/C setting just because the equipment is
an air conditioner and not a heat pump.
2.
ADVANCED SETUP:
from the main screen, press the
SCROLL (UP/DOWN) BUTTONS
to navigate through
the six (6) basic menu items to the
ADVANCED SETUP
menu.
– Push the
SELECT (ENTER) BUTTON
to choose the
ADVANCED SETUP
menu.
– Navigate through the multiple levels of
ADVANCED
SETUP
by pushing the
SCROLL (UP/DOWN)
BUTTONS
.
– To change a specific parameter in the
ADVANCED
SETUP
menu, press the
SELECT (ENTER)
BUTTON
to display its current value. Press the
SCROLL (UP/DOWN) BUTTONS
to change or
increase/decrease value. Press the
SELECT
(ENTER) BUTTON
to save the new customized
value—
“CHANGE STORED”
will be displayed.
Press the
SELECT (ENTER) BUTTON
again to
return to current menu parameter.
– For specific
ADVANCED SETUP
level information,
refer to
Table 3
.
*
*
3.
SETPOINTS:
from the main screen, press the
S
CROLL (UP/DOWN) BUTTONS
to navigate through the
six (6) basic menu items to the
SETPOINTS
menu.
– Push the
SELECT (ENTER) BUTTON
to choose the
SETPOINTS
menu.
– Navigate through the multiple levels of
SETPOINTS
by pushing the
S
CROLL (UP/DOWN) BUTTONS
.
– To change a specific parameter in the
SETPOINTS
menu, press the
SELECT (ENTER) BUTTON
to
display its current value. Press the
SCROLL (UP/
DOWN) BUTTONS
to change or increase/decrease
value. Press the
SELECT (ENTER) BUTTON
to save the new customized value—
“CHANGE
STORED”
will be displayed. Press the
SELECT
(ENTER) BUTTON
again to return to current menu
parameter.
– For specific
SETPOINTS
level information, refer to
Table 4
.
NOTE:
At this point, the economizer assembly should
be fully functional and ready for preliminary testing.