58
INSTALLATION AND OPERATING INSTRUCTIONS · HSI
EN
Solar Charging Mode
INVERTER MODEL
HSI 204/60 A
HSI 304/60 A
Max . PV Array Open Circuit Voltage Voc 100 VDC
Vmp PV Array MPPT Voltage Range
30 ~ 95 VDC
Min . battery voltage for PV charge
17 V DC
PV power max .
1500 W
Please follow below steps to implement PV module connection::
1 . Remove insulation sleeve 10 mm for positive and
negative conductors
2 . Check correct polarity of connection cable from PV
modules and PV input connectors . Then, connect
positive pole (+) of connection cable to positive pole (+)
of PV input connector . Connect negative pole (-) of connection cable to negative pole
(-) of PV input connector .
3 . Make sure the wires are securely connected .
Figure 13:
2 – 3 kVA