Blueridge BM18M23C Installation Manual Download Page 15

Revised 5/14/2020

NOTE: Gauge shown in Table 8.1 is for 50' run 

or less. For longer runs, consult an electrician.

NOTE: While connecting the wires, please

strictly follow the wiring diagram (found inside 

the electrical box cover).

Follow these instructions to prevent distortion 

when the compressor starts:
•  The unit must be connected to the main out-

let. Normally, the power supply must have a 

low output impedance of 32 ohms.

•  No other equipment should be connected to 

the same power circuit.

•  The unit’s power information can be found on 

the rating sticker on the product.

1.  Prepare the cable for connection

a.  You must first choose the right gauge wire 

before preparing it for connection.

b.  Refer to the table above for 50 foot and 

under. For over 50 foot runs, consult an 

electrician.

c.  Using wire strippers, strip the rubber jack-

et from both ends of signal cable to reveal 

about 6” of wire.

d.  Strip the insulation from the ends of the 

wires.

e.  Using a wire crimper, crimp u-lugs on the 

ends of the wires.

2.  Remove the electric cover of the outdoor 

unit. If there is no cover on the outdoor 

unit, disassemble the bolts from the main-

tenance board and remove the protection 

board. (See Fig. 8.1)

Wiring

Cover

Screw

3.  Connect the u-lugs to the terminals Match 

the wire colors/labels with the labels on 

the terminal block, and firmly screw the 

u-lug of each wire to its corresponding 

terminal.

4.  Clamp down the cable with designated 

cable clamp.

5.  Insulate unused wires with electrical tape. 

Keep them away from any electrical or 

metal parts.

6.  Reinstall the cover of the electric control 

box.

Page 15 

Table 8.1: Wire Gauge/ Amperage chart

Rated Current of

Appliance (A)

Wire Gauge

13 - 18

14

18 - 25

12

25 - 30

10

30 - 50

8

Fig 8.1

Summary of Contents for BM18M23C

Page 1: ...ual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor unit When installi...

Page 2: ...Table of Contents Installation Manual Safety Precautions 04 Accessories 05 Installation Overview 06 Specifications 07 Outdoor Unit Installation 08 1 5 2 3 4...

Page 3: ...erant Piping Connection 11 Test Run 22 Using the Automatic Wiring Piping Correction Function 23 Wiring 14 Wiring Diagrams 16 Refrigerant Handling 19 Procedure 19 Refrigerant chart 21 Adding refrigeran...

Page 4: ...it consider strong winds typhoons and earthquakes that might affect your unit and locate it accordingly 7 Do not use means to accelerate the defrosting process or to clean other than those recommended...

Page 5: ...selecting a suitable remote controller Name Shape Quantity Installation plate 1 Plastic expansion sheath 5 8 depending on models Self Tapping Screw A ST 3 9X25 5 8 depending on models Drain joint some...

Page 6: ...llation Overview INSTALLATION ORDER MC MC L N Install the indoor unit separate manual Install the outdoor unit Page 09 Connect the refrigerant pipes Page 12 Connect the wires Page 14 Perform a test ru...

Page 7: ...t feet 2 Zone 3 Zone 4 Zone 5 Zone Max length for all rooms 131 197 262 262 Max length for one indoor unit 82 98 115 115 Max height different between indoor and outdoor unit 49 49 49 49 Max height dif...

Page 8: ...bolts M10 The area must be free of combustible gases and chemicals The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length If possible avoid installing the...

Page 9: ...View All Condensers A B mount point dimensions W H W H A B D 10 feet or more 2 feet or more 5 feet or more 10 inches or more Model W D H A B BM18M23C 33 27 14 29 27 64 21 3 13 8 BM27M23C 37 2 16 5 31...

Page 10: ...e in the bas pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode You must drill a h...

Page 11: ...t leakage after completing the installation work Step1 Cut pipes When preparing refrigerant pipes take extra care to cut and flare them properly This will ensure efficient operation and minimize the n...

Page 12: ...shown in table 7 1 Step 4 Connect pipes Connect the copper pipes to the indoor unit first then connect it to the outdoor unit You should first connect the low pressure pipe then the high pressure pip...

Page 13: ...nit NOTE ON MINIMUM BEND RADIUS Carefully bend the tubing in the middle according to the diagram below DO NOT bend the tubing more than 90 or more than 3 times Bend the pipe with thumb min radius 3 9...

Page 14: ...ctrical shock Ensure that main supply connection is made through a switch that disconnects all poles with contact gap of a least 3mm 0 118 DO NOT modify the length of the power cord or use an extensio...

Page 15: ...s consult an electrician c Using wire strippers strip the rubber jack et from both ends of signal cable to reveal about 6 of wire d Strip the insulation from the ends of the wires e Using a wire crimp...

Page 16: ...ures if end users wish to perform their own wiring Run the main power cord through the lower line outlet of the cord clamp ____ This symbol indicates field wiring Wiring TO A 1 2 3 TO B 1 2 3 L1 L2 1...

Page 17: ...3 A 1 B 2 B 3 B 1 C 2 C 3 C L1 L2 1 A 2 A 3 A Ground POWER TO A 1 2 3 TO B 1 2 3 TO C 1 2 3 TO D 1 2 3 1 B 2 B 3 B 1 C 2 C 3 C 1 D 2 D 3 D L1 L2 1 A 2 A 3 A 1 B 2 B 3 B 1 C 2 C 3 C 1 D 2 D 3 D L1 L2 1...

Page 18: ...Revised 5 14 2020 Wiring TO E 1 2 3 TO C 1 2 3 TO D 1 2 3 TO A 1 2 3 TO B 1 2 3 Ground POWER 1 A 2 A 3 A 1 B 2 B 3 B 1 C 2 C 3 C 1 D 2 D 3 D 1 E 2 E 3 E L1 L2 Page 18 BM48M five zone condenser...

Page 19: ...ectrical capacity is sufficient Confirm that starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in th...

Page 20: ...manifold gauges Pressurize lineset to 200 psi of dry nitrogen 4 Check for leaks Spray soap bubbles on fit tings at outdoor and indoor units to check for bubbles leaks If leaks are present retorque fla...

Page 21: ...gauges in place Follow the remaining steps to test run the system and add refrigerant if needed 12 Record Pressure Start the unit in cooling mode Run for 10 minutes and monitor oper ating pressure re...

Page 22: ...igerant charging must be performed after wiring leak testing and vacuuming DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system Doing so can damage the unit or impact i...

Page 23: ...nnected h Length of the piping and additional refrigerant stow capacity have been recorded i The power voltage is the correct voltage for the air conditioner 1 Open both the liquid and gas stop valves...

Page 24: ...piping error is corrected and all wiring piping is properly connected 1 Check that outside temperature is above 5o C This function does not work when outside temperature is not above 5o C 2 Check tha...

Page 25: ...The design and specifications are subject to change without prior notice for product improvement AlpineHomeAir com...

Reviews: