5
5.2
5.1
. Trouble Shooting Steps
Problem determination based on:
1) Whether the battery can be turned on.
2) If battery is turned on, check the red light is off, flashing or lighting;
3) If the red light is off, check whether the battery can be charged/discharged.
Preliminary determination steps:
1) Battery cannot be turned on, switch on the lights are all no lighting or flashing.
If the battery external switch is ON, the RUN light is flashing, and the external power supply
voltage is 48V or more, the battery still unable to turn on, please contact distributor.
2)
The battery can be turned on, but red light is lighting, and cannot be charged or discharged,
red light is lighting, that means system is abnormal, please check values as following:
a) Temperature: Above 50 or under -10 , the battery could not work.
Solution: to move battery to the normal operating temperature range between -10 and 50
b) Current: If current is larger than 100A, battery protection will turn on.
Solution: Check whether current is too large or not, if it is, to change the settings on power
supply side.
c) High Voltage: If charging voltage above 54V, battery protection will turn on.
Solution: Check whether voltage is too high or not, if it is, to change the settings on power
supply side.
d) Low Voltage: When the battery discharges to 44.5V or less, battery protection will turn on.
Solution: Charge the battery for some time, the red light will turn off.
Excluding the four points above, if the faulty is still cannot be located, turn off battery and repair.
if the
energía indoor
www.Latpower.com