Blue-White ProSeries SONIC-PRO S4 Series Installation And Operating Manual Download Page 20

 

 

Page 19

Sonic-Pro

Page 20

Sonic-Pro

6.4.1
Analog 
4-20mA
Output Menu

An analog current output signal can be programmed within the range of 4-20mA. 

Specify the flow rate at a minimum current (

Rate at Min Curr.) 

and the corresponding 

minimum analog current (

Min Analog O/P). 

Specify the flow rate at a maximum current (

Rate at Max Curr.) 

and the corresponding 

maximum analog current (

Max Analog O/P). 

The flow rates must not be the same. The current for the high flow rate may be smaller than 
the current for the low flow rate in which case, the current will decrease with increasing flow 
rate.

Flow rates are mapped to currents using a straight line through the two points specified. 

Analog 4-20mA

Rate at Min Curr.

0.0000

Enter Value

Min Analog O/P

4

Enter Value

Rate at Max Curr.

0.0000

Enter Value

Max Analog O/P

20

Enter Value

6.4.2
Pulse 
0-1000 Hz
Output Menu

A digital pulse output signal can be programmed within the range of 0-1000 Hz (pulses per 
second).

Specify the flow rate at a minimum frequency (

Rate at Min Freq.) 

and the corresponding 

minimum frequency (

Min Frequency). 

Specify the flow rate at a maximum frequency (

Rate at Max Freq.) 

and the corresponding 

maximum frequency  (

Max Frequency). 

The flow rates must not be the same. The frequency for the high flow rate may be smaller 
than the frequency for the low flow rate in which case, the frequency will decrease with 
increasing flow rate.

Flow rates are mapped to frequencies using a straight line through the two points specified. 

Pulse 0-1000

Rate at Min Freq.

0.0000

Enter Value

Min Frequency

0

Enter Value

Rate at Max Freq.

0.0000

Enter Value

Max Frequency

1000

Enter Value

6.4.3
Contact
Closure
Relay
Output Menu

The S4 has two Form C relays. Each can be independently configured to energize when one 
of the following conditions are met: 

!

A specific 

Flow Rate

 value is displayed, used for high, low or high/low range alarms.

!

An 

Accumulated Total

 value has been measured. Used for triggering external equipment 

when a configured batch amount is reached.

!

FAULT 

has occurred.

Contact Closure

Relay A

Monitor Flow Rate

High Trigger A

0

Enter Value

High Release A

0

Enter Value

Low Trigger A

0

Enter Value

Low Release A

0

Enter Value

Time(s) A

0

Enter Value

Monitor Totalizer

Batch Amt. A

0

Enter Value

Contact Timer(s) A

0

Enter Value

Faults A

Relay B

Monitor Flow Rate

High Trigger B

0

Enter Value

High Release B

0

Enter Value

Low Trigger B

0

Enter Value

Low Release B

0

Enter Value

Time(s) B

0

Enter Value

Monitor Totalizer

Batch Amt. B

0

Enter Value

Contact Timer(s) B

0

Enter Value

Faults B

None A

None B

Relay B

Monitor Flow Rate

High Trigger B

0

Enter Value

High Release B

0

Enter Value

Low Trigger B

0

Enter Value

Low Release B

0

Enter Value

Time(s) B

0

Enter Value

None B

6.4.3.1
CC Assigned to
Monitor Flow Rate

When in the 

Relay A 

or 

Relay B 

menu, selecting and then exiting the 

Monitor Flow Rate 

menu will assigned that relay to monitor the rate of flow. The following functions are possible:

!

Set a 

High Trigger

 flow rate value which when measured, will energize the relay.

!

Set a 

High Release 

flow rate value which when measured, will de-energize the relay. 

!

Set a 

Low Trigger

 flow rate value which when measured, will energize the relay.

!

Set a 

Low Release 

flow rate value which when measured, will de-energize the relay.  

!

Set a 

Time (s) 

in seconds (0-999) to delay energizing the relay when it is triggered.

When either of the relays are energized, the display back-light will turn blue.

When both the trigger and release values are configured for the same value, the relay will 
latch. The user must press the 

ESC 

button to clear a latched relay.

Industries, Ltd.

Industries, Ltd.

ProSeries

by Blue-White Ind.

d

Industries, Ltd.

Industries, Ltd.

ProSeries

by Blue-White Ind.

d

Summary of Contents for ProSeries SONIC-PRO S4 Series

Page 1: ...Installation and Operating Manual 2 TWO YEAR WARRANTY ProSeries Series S4 Ultrasonic Flow Meter Industries Ltd Industries Ltd ProSeries by Blue White Ind d SONIC PRO d...

Page 2: ...DING THE SAFE USE OF THIS PRODUCT AND OTHER TECHNICAL ASSISTANCE MAY BE DIRECTED TO Blue White Industries 714 893 8529 techsupport blue white com CAUTION risk of electric shock CAUTION risk of danger...

Page 3: ...ions of other chemicals or other chemicals entirely may be acceptable provided the chemical does not change the sound speed SOS more than approximately 100 meters per second and provided the fluid all...

Page 4: ...must not be cut or modified Note that the Sonic Pro can accurately measure flow from either direction The SPU can be mounted on a wall or on a horizontal or vertical run of pipe Although the Sonic Pro...

Page 5: ...is required on downward flows to ensure a full pipe See the minimum straight length of pipe requirement chart above Related piping must be independently supported The meter should not be allowed to s...

Page 6: ...d tight cable gland connectors for cable diameter from 200 to 394 inches 5 1 to 10 0 mm Two liquid tight cable gland connectors cable for diameters from 118 to 255 inches 3 0 to 6 5 mm One communicati...

Page 7: ...ector T2 1 2 Positive Negative Type Open collector w internal 1 K pull up to 5V Can be pulled up to 30V 10mA 3K pull up Duty Cycle 50 5 Frequency Range 0 1000 Hz Resolution 1 Hz Accuracy 0 5 F S PADDL...

Page 8: ...allowable SOS Speed Of Sound error set point has been exceeded FAULT 21 The configuration data is not valid Flow Direction Total Units U S Gallons Min 105 1482 25 05 469 U S Gallons 0 28 Transducer S...

Page 9: ...he value Press ENTER to confirm the modifications and return to the menu heading Press ESC to cancel the modifications and return to the menu heading 5 3 2 Selecting Optional Items Press up arrow p or...

Page 10: ...use your inlet outlet pipe material 10 Fluid Type Select WATER or CUSTOM 11 Fluid SOS If WATER is selected it is not necessary to input a fluid SOS If CUSTOM fluid type is selected the Speed of Sound...

Page 11: ...e factory set inside the pipe fitting and cannot be moved Select the mount method that is shown on the Calibration Detail label affixed to the pipe fitting Transducer Model I C J Mount Method W V Cabl...

Page 12: ...ings Direction Zero A B Scaling A B Enter Value Sign A B Zero Value A B Positive B A A B Enter Value Zero B A Scaling B A Enter Value Sign B A Zero Value B A Enter Value 0 975 0 455 Negative Positive...

Page 13: ...n the acceptable range and there are not too many particles or other sound blocking or reflecting contaminants in the fluid which can inhibit the sound beam The target Fluid SOS value can be adjusted...

Page 14: ...els Oil Cubic Feet Acre Feet Imperial Gallons Cubic Meters Liters Milliliters FR Custom V Gal Fl Total Decimal 0 Enter Value Flow Average s 0 Enter Value Enable Tot Clear Yes No Low Fl Cut Off 0 Enter...

Page 15: ...into any Tot Set Point 1 2 3 4 or 5 a new log will be generated when the total accumulated flow value is equal to the configured value To access the log entries you must copy the logs onto a USB flash...

Page 16: ...ters Milliliters TOT Custom V Gal Fl Total Decimal 0 Enter Value Flow Average s 0 Enter Value Enable Tot Clear Yes No Low Fl Cut Off 0 Enter Value High Fl Cut Off 999 Enter Value Scaling Off set 1 000...

Page 17: ...Off value totalizing will still occur 6 3 2 6 High Flow Rate Cut off Setting High Fl Cut Off 999 Enter Value Scaling Off Set is a multiplier used to correct for flow inaccuracies All flow rate values...

Page 18: ...e meter was sleeping using the following formula Total flow display value T1 F1 F2 2 x N 1 Where T1 Last total before sleep F1 Last flow rate units per second before sleep F2 Flow rate average of the...

Page 19: ...gh Release A 0 Enter Value Low Trigger A 0 Enter Value Low Release A 0 Enter Value Time s A 0 Enter Value Monitor Totalizer Batch Amt A 0 Enter Value Contact Timer s A 0 Enter Value Faults A Relay B M...

Page 20: ...ue Rate at Max Curr 0 0000 Enter Value Max Analog O P 20 Enter Value 6 4 2 Pulse 0 1000 Hz Output Menu A digital pulse output signal can be programmed within the range of 0 1000 Hz pulses per second S...

Page 21: ...ue Faults B None A None B Relay B Monitor Flow Rate High Trigger B 0 Enter Value High Release B 0 Enter Value Low Trigger B 0 Enter Value Low Release B 0 Enter Value Time s B 0 Enter Value None B 6 4...

Page 22: ...Value Contact Timer s B 0 Enter Value 6 4 3 2 CC Assigned to Monitor FAULTS When in the Relay A or Relay B menu selecting and then exiting the FAULTS menu will assign that relay to energize when any...

Page 23: ...unsigned char 8 Frequency output 45 Firmware Version unsigned char 8 8 ASCII characters A11 22 33 53 Log Entry unsigned char 86 Log Entry String Eg 2013 12 29 09 15 00 FR 0 0000 TL 0 00 Description P...

Page 24: ...e meter can be re calibrated in the field by selecting Calibration and pressing the right arrow u or ENTER button The pipe must be full of fluid and there must be no movement of the fluid in the pipe...

Page 25: ...Save Config function is possible at the main menu Global Config Password 1234 Enter Value Change Password Change Password Old Pass 1234 OK CANCEL NEW Pass 5678 OK Enter master password 3408 to clear a...

Page 26: ...me Units Independently configurable Rate and Total display units in U S Gallons ounces barrels US liquid barrels US oil cubic ft acre ft Imperial British gallons liter cubic meter or user defined cust...

Page 27: ...ipe fitting transducer no transducer cables Standard 4 20mA and High Speed Pulse output only Without power supply customer supplies 15 30 VDC 0 25 ft cable length with field replaceable liquid tight c...

Page 28: ...03 5 41 1427 10 50 1447 20 68 1481 30 86 1507 40 104 1526 50 122 1541 60 140 1552 70 158 1555 80 176 1555 90 194 1550 100 212 1543 Water Sound Speeds 7 2 Sound speed data Page 27 Sonic Pro Industries...

Page 29: ...in 18 39cm 5 90in 14 97cm 74in 1 88cm 2 75in 6 99cm 7 24in 18 39cm 5 83in 14 80cm 55in 1 39cm 2 75in 6 99cm Sonic Pro Inline Pipe Fittings Pipe Size 2 1 5 1 75 5 Pipe Size OL OW A B C 2 7 47in 18 97cm...

Page 30: ...ers TOT Custom V Gal Fl Total Decimal 0 Enter Value Flow Average s 0 Enter Value Enable Tot Clear Yes No Low Fl Cut Off 0 Enter Value High Fl Cut Off 999 Enter Value Scaling Off set 1 0000 Enter Value...

Page 31: ...Enter Value Time s B 0 Enter Value Monitor Totalizer Batch Amt B 0 Enter Value Contact Timer s B 0 Enter Value Faults B Clock CLOCK SET 2013 07 24 14 31 OK CANCEL Calibration Clear Cal Value None A N...

Page 32: ...kmanship for 24 months from date of factory shipment WARRANTY COVERAGE IS LIMITED TO REPAIR OR REPLACEMENT OF THE DEFECTIVE FLOWMETER ONLY UNDER NO CIRCUMSTANCES SHALL BLUE WHITE BE LIABLE FOR ANY CON...

Reviews: