Installation and Operation Manual
14
¾
PRECAUCIÓN:
La unidad está protegida contra polaridad invertida de la batería y del conjunto
fotovoltaico, pero no está protegida contra una batería en reversa conectada a los terminales
fotovoltaicos. Un daño de este tipo anulará la garantía limitada.
SETUP AND WIRING DIAGRAM
FIGURE 3
ELECTROSTATIC HANDLING PRECAUTIONS
Discharge yourself by touching a water faucet or other electrical ground prior to handling the unit and avoid touching
components on the circuit boards. Keep the Digital Display in it’s electrostatic protective bag until it is installed. All electronic circuits
may be damaged by static electricity. The risk of electrostatic damage is highest when relative humidity is below 40%.
MAXIMUM PV SHORT CIRCUIT CURRENT AND NEC
To be compliant with National Electrical Code (NEC), solar module controllers should be sized for 125% more rated capacity than
the 25
°
C short circuit current (I
SC
) rating of the PV modules, and then all components be sized another 125% greater. However,
since the Solar Boost 50 is qualified for continuous use at 60 amp output, only a single 125% derating factor is required.