PART 12.Common Fault Analysis Table
LED and buzzer combination status table
LIN
INV
BAT
Load
TEMP
Beep
AC Mains output
ON
OFF
Inverter output
OFF
ON
DC overvoltage
1s 1flash
1s 1 buzzer
DC lower voltage
3s 1flash
3s 1 buzzer
Overload 150%
ON
Without stopping buzzer
Overload 125~150%
1s 1flash
1s 1 buzzer
Overload 100~125%
3s 1flash
3s 1 buzzer
Over temperature
1s 1flash
1s 1flash
1s 1flash
1s 1 buzzer
Inverter failure
ON
ON
ON
Without stopping buzzer
Remark
1.
Blank form indicates mean that it should be refer to related items
2.
For example: "LINE" is ON, "INV" is OFF, "BAT" flashes for 1 second, "Load" goes off, and buzzer sounds for 1 second. IT
means In the ac output state, DC input over voltage, normal load, no over temperature
Fault Analysis Table
1.
When the inverter fails, the red signal indicator on the front panel will be “ON”
2.
According to different fault conditions appear as long and alarm or flashing.
3.
You can determine the cause of the fault by looking at the indicators on the front panel and refer to the following
figure for proper handling.
Item
Fault
Possible Reason
Solutions
1
Battery, load, over
temperature LED, 1s 1 flash
Turn off the output due to internal
overheating
1.
Check the fan is running or not
2.
Check the air vents are blocked or not
3.
The environment temperature is too high or not
4.
Reduce the load
5.
Wait 10 minutes for inverter cooling and drop of
the temperature then restart
2
The load LED Indicator ON
and the buzzer sounds
1.
Overload more than 150%
2.
Internal failure to shut down
the inverter
1.
Check whether running in overload
2.
If yes, Reduce the load and restart
3
Battery LED Indicator ON.
3s1 flash, buzzer 3s 1 sound
Input DC voltage is too lower
Check the DC input voltage is too lower and out of
the range for the inverter requirements
4
Battery LED Indicator ON.
1s1 flash, buzzer 1s 1 sound
Input DC voltage is too higher
Check the DC input voltage is too higher and out of
the range for the inverter requirements
5
Load LED Indicator, 3
seconds 1 flash, buzzer 3
seconds 1 sound
Overload 100~125%
1.
Check whether running in overload
2.
If yes, Reduce the load and restart
6
The LINE Indicator OFF
after connect with AC City
main Power
AC Mains voltage and frequency
exceed the input limited range
1.
Check if the AC mains voltage and frequency
exceed the inverter input range.
2.
Check whether the power switch on the panel is
switch on or not .