PART 12.Common Fault Analysis Table 

 

LED and buzzer combination status table   

 

LIN 

INV 

BAT 

Load 

TEMP 

Beep 

AC Mains output 

ON 

OFF 

 

 

 

 

Inverter output 

OFF 

ON 

 

 

 

 

DC overvoltage 

 

 

1s 1flash 

 

 

1s 1 buzzer 

DC lower voltage 

 

 

3s 1flash 

 

 

3s 1 buzzer 

Overload 150% 

 

 

 

ON

 

 

Without stopping buzzer 

Overload 125~150% 

 

 

 

1s 1flash 

 

1s 1 buzzer 

Overload 100~125% 

 

 

 

3s 1flash 

 

3s 1 buzzer 

Over temperature 

 

 

1s 1flash 

1s 1flash 

1s 1flash 

1s 1 buzzer 

Inverter failure 

 

 

ON 

ON 

ON 

Without stopping buzzer

 

Remark   

1.

 

Blank form indicates mean that it should be refer to related items 

2.

 

For example: "LINE" is ON, "INV" is OFF, "BAT" flashes for 1 second, "Load" goes off, and buzzer sounds for 1 second. IT 

means In the ac output state, DC input over voltage, normal load, no over temperature 

 

Fault Analysis Table 

1.

 

When the inverter fails, the red signal indicator on the front panel will be “ON”

 

2.

 

According to different fault conditions appear as long and alarm or flashing.

 

3.

 

You can determine the cause of the fault by looking at the indicators on the front panel and refer to the following 

figure for proper handling.

 

 

Item 

Fault 

Possible Reason 

Solutions 

Battery, load, over 

temperature LED, 1s 1 flash 

Turn off the output due to internal 

overheating 

1.

 

Check the fan is running or not 

2.

 

Check the air vents are blocked or not 

3.

 

The environment temperature is too high or not 

4.

 

Reduce the load 

5.

 

Wait 10 minutes for inverter cooling and drop of 

the temperature then restart 

The load LED Indicator ON 

and the buzzer sounds 

1.

 

Overload more than 150% 

2.

 

Internal  failure  to  shut  down 

the inverter 

1.

 

Check whether running in overload 

2.

 

If yes, Reduce the load and restart 

Battery LED Indicator ON. 

3s1 flash, buzzer 3s 1 sound 

Input DC voltage is too lower 

Check  the  DC  input voltage  is too  lower  and  out  of 

the range for the inverter requirements 

Battery LED Indicator ON. 

1s1 flash, buzzer 1s 1 sound 

Input DC voltage is too higher 

Check the DC input voltage is too higher and out of 

the range for the inverter requirements 

Load LED Indicator, 3 

seconds 1 flash, buzzer 3 

seconds 1 sound 

Overload 100~125% 

1.

 

Check whether running in overload 

2.

 

If yes, Reduce the load and restart 

The LINE Indicator OFF 

after connect with AC City 

main Power 

AC Mains voltage and frequency 

exceed the input limited range 

1.

 

Check  if  the  AC  mains  voltage  and  frequency 

exceed the inverter input range. 

2.

 

Check whether the power switch on the panel is 

switch on or not . 

Summary of Contents for OPT-R 110V Series

Page 1: ...ual Tel 0086 023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 OPT R 0 5KVA 10KVAPure Sine Wave Inverter User Manual 19 Rack mount ...

Page 2: ...ther electrical equipment To prepare for the instability of the city electricity and power cuts It also prevents various distortions of utility power such as power supply voltage drop surge voltage spike voltage and broadcast frequency interference PART 2 Customized Range Input Output voltage Capacity 19Inch 1U 2U 4U Rack Mount With LCD LED Display With RS232 Communication port Power Factor 0 8 Wi...

Page 3: ...t voltage and frequency 220Vac 50Hz Rate output current A 1 8 3 6 7 2 10 8 14 5 18 2 21 8 29 36 3 Output voltage accuracy V 220 3 Output frequency accuracy Hz 50 0 1 Waveform distortion rate THD 3 Linear load Dynamic Response 5 Load 25 100 Power Factor PF 0 8 Over load ability 100 125 10mins 125 150 15seconds 150 shut down Immediately Efficiency 85 80 Resistive load Bypass conversion time ms 5ms O...

Page 4: ...6 6 2 KVA 8 3 2 KVA 7 8 3 KVA 117 3 KVA 57 3 KVA 24 9 3 KVA 12 4 3 KVA 11 7 4 KVA 77 4 KVA 33 4 4 KVA 16 7 4 KVA 15 6 5 KVA 98 5 KVA 36 6 5 KVA 18 3 5 KVA 19 6 6 KVA 117 6 KVA 51 3 6 KVA 22 6 KVA 23 5 8 KVA 156 8 KVA 68 8 KVA 34 2 8 KVA 34 2 10 KVA 196 10 KVA 85 10 KVA 42 7 10 KVA 39 Remarks 1 Due to the difference in the instrument used during the test the range points may be slightly deviated 2 ...

Page 5: ...hree pages on the LCD screen and each page shows two lines of content First page Output voltage XXX X Vac Load ratio XXX Second page DC input XXX X Vdc AC input XXX X Vac Third page Load power XX XX kW Output frequency XX X Hz 3 BLA Backlight button Press the backlight key BLA the backlight is on 4 LIN AC City Power indicator The LIN Indicator ON Mean the inverter work in AC input and ac output in...

Page 6: ...eck the packing of the goods when receiving the goods that the goods company is carrying In case of any damage please indicate on the receipt Storage Keep it in a cool dry ventilated place away from highly corrosive dusty hot and humid environments If you do not use the inverter for a long period of time you should be able to use it every 6months Check the machine nameplate Check if the specificat...

Page 7: ...023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 PART 8 Appearance Dimension 19inch 1U Rack Mount Front Rear View 500VA 2000VA Front Rear View ...

Page 8: ...ser Manual Tel 0086 023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 3KVA 6KVA Front Rear View 8KVA 10KVA Front Rear View ...

Page 9: ... 023 67628702 Email tech cqbluejay com www cqbluejay com Add Block 3A 13 25 No 153 Jingyu Avenue Jiangbei Qu Chongqing City 401147 PART 9 Wiring diagram description 1U Rack Mount type 2U Rack Mount type 4U Rack Mount type ...

Page 10: ... the inverter after switch DIP switch if not it did not work Switch the DIP switch to the digital side is 1 Switch the DIP switch to the NO side is 0 0000 1111 Noted Connect the inverter with the Earth is necessary to make sure it can safety and normal operation of the inverter and reduce electromagnetic interference The grounding wire must be grounded GND and the earth grounding terminal should b...

Page 11: ... following figure for proper handling Item Fault Possible Reason Solutions 1 Battery load over temperature LED 1s 1 flash Turn off the output due to internal overheating 1 Check the fan is running or not 2 Check the air vents are blocked or not 3 The environment temperature is too high or not 4 Reduce the load 5 Wait 10 minutes for inverter cooling and drop of the temperature then restart 2 The lo...

Page 12: ...r internal circuit are broken or short circuit 9 Can not switch the dc and bypass in automatic 1 AC Mains voltage and frequency exceed the Inverter input limited range 2 The dial switch DIP Switch on the rear panel is set to the wrong position 1 Check whether the ac mains voltage and frequency exceed the input range of the inverter 2 Check whether the dial switch DIP Switch in the corresponding po...

Reviews: