Note:
Not all PR200 series have above complete configuration menus, please confirm your
purchased PR200 sub-code, if do not have the corresponding extension module. In
configuration menu corresponding part is invalid.
5.6- Example of programming menu operation
5.6.1- Set sampling input value
Step1: Press Menu enter configuration menu; device ask password;
Step2: Press
for entry password, use key ← & → to input password
0012
, will move to
Level-1 configuration menu;
Step3: Press
to enter level-2 of “
Signal Input
” menu, to set Input current range “
InPt
”;
Step4: Press
enter level-3 value range selecting, you can see default current range “
5A
”;
Step5: Press← or → to select input current range, in example use “
10A
”;
Step6: Press
to confirm the modify and return to the previous level menu;
Step7: Press Menu for roll back to the level-1 menu;
Step8: Press Menu for exit configuration to the monitor screen;
Step9: Main screen show “SAVE”, press
for save the change and exit configuration;
press Menu for exit without save.