Operating Instructions and Parts Manual

Symptom

Possible Cause(s)

Corrective Action

Troubleshooting Chart

Motor will not run

Motor runs hot and
overload kicks off

Motor runs but no
water is delivered
Note: Check prime
before looking for
other causes. Unscrew
priming plug and see if
water is in priming
hole.

Pump does not deliver
water to full capacity

1. Disconnect switch is off

2. Defective wiring

1. Voltage is too low

2. Pump house not properly

vented

1. Pump in new installation

did not pick up prime
through:
a. Improper priming
b. Air leaks
c. Leaking foot valve

2. Pump has lost prime

through:
a. air leaks
b. water level below suc-

tion of pump

3. Impeller is plugged
4. Check valve or foot valve

is stuck in closed position

5. Pipes are frozen

6. Foot valve and/or strainer

are buried in sand or mud

1. Water level in well is

lower than estimated

2. Steel piping (if used) is

corroded or limed, causing
excess friction

3. Piping is too small in size

1. Be sure switch is on

2. Refer to instructions.  Check all connections

1. Check with power company. Use heavier gauge cord

2. Be sure pump has sufficient ventilation to cool the motor

1. New installation:

a. Re-prime according to instructions
b. Check all connections on suction line
c. Replace foot valve

2. Existing installations:

a. Check all connections on suction line and shaft seal
b. Lower suction line into water and re-prime. If receding

water level in well exceeds suction lift, a deep well pump is
needed

3. Clean impeller
4. Replace check valve or foot valve

5. Thaw pipes. Bury pipe below frost line. Heat pit or pump

house

6. Raise foot valve and/or stainer above well bottom

1. A deep well jet pump my be needed (over 25 ft. (7.6M) to

water)

2. Replace with plastic pipe where possible, otherwise with new

steel pipe 

3. Use larger piping

BPLS Series

www.blueangelpumps.com

Summary of Contents for BPLS Series

Page 1: ...mp flammable or explosive fluids such as gasoline fuel oil kerosene etc Do not use in a flamma ble and or explosive atmosphere Personal injury and or property dam age could result This pump is not des...

Page 2: ...ure 1 BOOSTING WATER PRESSURE Do not run pump with outlet pipe or nozzle closed The hose may burst from excessive pressure Use only reinforced high pressure hose or pipe for outlet pipe 1 Connect inle...

Page 3: ...er level in well is lower than estimated 2 Steel piping if used is corroded or limed causing excess friction 3 Piping is too small in size 1 Be sure switch is on 2 Refer to instructions Check all conn...

Page 4: ...AND FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED TO ONE YEAR FROM THE DATE OF PURCHASE THIS IS THE EXCLUSIVE REMEDY AND ANY LIABILITY FOR ANY AND ALL INDIRECT OR CONSEQUENTIAL DAMAGES OR EXPENSES WHA...

Page 5: ...autre application qui pourraient contenir des produits chi miques caustiques et ou des mati res trang res Des dommages la pompe pourraient d couler si utilis e dans ces applications et cela annulera...

Page 6: ...PVC ou un boyau de jardinage peut servir Un adapta teur pour le filetage du boyau de jardinage est inclus figure 1 RENFORCER LA PRESSION D EAU Ne pas faire fonc tionner la pompe avec un tuyau de sor t...

Page 7: ...orrod ou chaul provoquant une friction suppl mentaire 3 Le conduit est trop petit 1 S assurer que l interrupteur est en marche 2 Refer to instructions Check all connections 1 V rifier aupr s de la soc...

Page 8: ...ADAPTATION UNE FONCTION PARTICULI RE SONT LIMIT ES UN AN COMPTER DE LA DATE D ACHAT CECI EST LE SEUL RECOURS EXCLUSIF ET TOUTE AUTRE RESPONSABILIT POUR TOUT AUTRE DOMMAGE QUELCONQUE INDIRECT OU D PENS...

Page 9: ...sto podr a ocasionarle heridas y o da os a su propiedad Esta bomba no est dise ada para bombear agua salada salmuera agua con deter gentes o para ning n tipo de aplicaci n donde el agua pueda contener...

Page 10: ...exi n a tierra y un enchufe de uni n del tipo de cone xi n a tierra Use un recept cu lo con conexi n a tierra para reducir el riesgo de choque el ctrico mortal Nunca corte la pata redonda de conexi n...

Page 11: ...zadas ocasionando fricci n excesiva 3 Las tuber as son muy peque as 1 Cerci rese de que el interruptor est en ON encendido 2 Refer to instructions Check all wiring connections 1 Cons ltele a la compa...

Page 12: ...ARANTIAS EXPRESAS LAS GARANTIAS IMPLICITAS INCLUYENDO GARANTIAS EN RELACION AL MERCADEO O USOS ESPECIFICOS ESTAN LIMITADAS A UN A O A PARTIR DE LA FECHA DE COMPRA ESTA ES LA UNICA GARANTIA DISPONIBLE...

Reviews: