Blue Angel Pumps 100SW Operating Instructions And Parts Manual Download Page 7

INSTALLATION MANUAL

7

TROUBLESHOOTING CHART (CONT’D)

Symptoms

Possible Cause(s)

Suggested Remedies

Pump trips GFCI 1.  Bad GFCI

2.  Bad pump

1.  Contact an electrician to replace GFCI
2.  Replace pump 

Pump operates 
noisily or vibrates 
excessively

1.  Worn bearings
2.  Impeller broken
3.  Piping attachments to building 

structure too rigid or too loose

1.  Replace pump
2.  Replace pump
3.  Install rubber coupling (available at local hardware stores) to isolate 

pump vibration from discharge plumbing

Pump will not 
shut off

1. Switch
2.  Switch obstructions
3.  Restricted discharge (obstruction in 

piping)

4.  Excessive inflow or pump not 

properly sized for application

1.  Replace tether switch
2.  Remove obstruction to verify free motion of switch
3.  Remove obstruction from discharge piping

4.  Recheck all sizing calculations to determine proper pump size

Pump operates 
but delivers little 
or no water

1.  Low supply voltage
2.  Inlet clogged
3.  Broken impeller
4.  Pump not properly sized for 

application

5.  Check valve stuck closed or 

installed backwards

6.  Shut off valve closed

1.  Contact an electrician
2.  Remove debris
3.  Replace pump
4.  Recheck all sizing calculations to determine proper pump size

5.  Remove and examine check valve for proper installation and free 

operation

6.  Open valve

ROUTINE MAINTENANCE

The pump should be inspected 3-4 times per year for pump movement or buildup of debris on the switch or float. Reposition 
pump if it has moved. Remove any debris that could interfere with the operation of the switch. Lack of proper routine maintenance 
will void warranty.

•   Make sure the pump is plugged in to a working ground fault circuit interrupter (GFCI) outlet and the cord is in good shape. In 

damp areas, GFCI breakers may trip, effectively shutting off the effluent pump. Check in on your sewage pump and reset the 
GFCI if necessary.

•  Ensure the pump is standing upright. Vibrations during operation can cause it to fall or tilt onto one side. This can jam the float 

so it can’t activate the pump.

•  Pour a bucket of water into the pit to make sure the pump starts automatically and the water drains quickly once the pump is 

on. If the pump doesn’t start, have it serviced or replaced.

•  Replace the tether switch every two (2) years. This maintenance will reduce the risk of improper pump operation, switch failure 

and/or flooding.

Summary of Contents for 100SW

Page 1: ...0SW F50SW Cast Iron 200SW 100SW 75SW SHAFT Steel DISCHARGE 2 in NPT T50SW F50SW 3 in NPT supplied 2 in Adapter 200SW 100SW 75SW Sewage Pump www blueangelpumps com Intended for Indoor Use Only T50SW Te...

Page 2: ...ompe est fournie avec un conducteur et une fiche de mise la terre Pour r duire le risque de choc lectrique s assurer qu elle est branch e seulement une prise de courant correctement mise la terre FOR...

Page 3: ...ACHEMINEMENT D EAU DESTIN E LA CONSOMMATION Ne pas utiliser la pompe pour transporter de l eau qui sera utilis e comme de l eau potable destin e la consommation La pompe doit tre utilis e uniquement d...

Page 4: ...USED when risk of property damage from high water levels exists UNE ALARME AUTONOME DE NIVEAU D EAU LEV OU UNE POMPE DE SAUVEGARDE DOIVENT TRE UTILIS ES en cas de risque de d g ts mat riels caus s par...

Page 5: ...to the side wall of the basin and is free of any possible obstructions 6 Install discharge plumbing according to local regional and state codes Do not reduce the discharge pipe 3 size below that whic...

Page 6: ...otion of switch 3 Remove obstruction in discharge piping 4 Contact an electrician TROUBLESHOOTING WARNINGS ALWAYS DISCONNECT THE PUMP FROM POWER SUPPLY before installing servicing or making any adjust...

Page 7: ...Contact an electrician 2 Remove debris 3 Replace pump 4 Recheck all sizing calculations to determine proper pump size 5 Remove and examine check valve for proper installation and free operation 6 Ope...

Page 8: ...WARRANTY SERVICE PARTS SHEET REPLACEMENT PARTS 8 1 2 REPAIR KITS REF NO DESCRIPTION PART NUMBER 1 20 FT POWER CORD 31006 WYN1 2 Tether Float Switch Kit T50SW Only 66051 WYN1...

Page 9: ...EXPRESSED OR IMPLIED INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE AND ANY RIGHTS OR REMEDIES AGAINST ANY PERSON OR ENTITY UNDER THE UNIFORM COMMERCIAL CODE...

Page 10: ...10 NOTES...

Page 11: ...11 NOTES...

Page 12: ...12...

Reviews: