- 14 -
Test Mode D16-D20
D16 Core temperature
This function is not available on B models.
C and K models can use only one core temperature probe, it is possible, however, to test
core temperature probes 1 and 2.
Here it is possible to read the current temperature of the core temperature sensor, P2 + P2A.
In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor
circuit is defective.
In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown.
To adjust the temperature, press the time key until the digit in the display flashes. Then adjust
upwards or downwards until the correct temperature is shown. Finally, press the time key again to
save the setting.
The temperature can be adjusted by +- 50°F (10°C).
You change between the various measuring points of the core temperature probe by pressing the
step key.
1= Core temp probe 1, point 1, 2= Core temp probe, point 2, 3= Core temp probe 1, point 3.
4= Core temp probe 2, point 1, 5= Core temp probe, point 2, 6= Core temp probe 2, point 3.
D17 Steam generator temperature
Available on K models only.
Here it is possible to read the current steam generator temperature, P3.
In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor
circuit is defective.
In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown.
To adjust the temperature, press the time key until the digit in the display flashes. Then adjust
upwards or downwards until the correct temperature is shown. Finally, press the time key again to
save the setting.
The temperature can be adjusted by +- 50°F (10°C).
D18 Drain temperature
Here it is possible to read the current steam generator temperature, P4.
In the field next to ”Temperature”, the current temperature is shown. If ERR appears, the sensor
circuit is defective.
In the field next to ”Time”, an adjustment value between 80 and 120 (default 100) is shown.
To adjust the temperature, press the time key until the digit in the display flashes. Then adjust
upwards or downwards until the correct temperature is shown. Finally, press the time key again to
save the setting.
The temperature can be adjusted by +- 50°F (10°C) (approx. 2°F (.5°C) per step).
D20 Door sensor
Here it is possible to read the status of and calibrate door sensor 1 = SE1 and 2 = SE1A.
You change between door sensor 1 and 2 by pressing the step key.
After some time, the text “DOOR SENSOR” changes to show the status of the sensor: >CLOSED<,
>OPEN<, >SENS ERROR<. You start the calibration by pressing the exhaust key.
How to calibrate:
1.
Press the damper key
2.
>CLOSE< flashes
3.
Close the door
4.
Press the damper key
5.
>OPEN< flashes
6.
Open door in the first step
7.
Press the damper key
8.
>CALIB OK< or >CALIB ERR< appears
9.
Press the damper key to confirm
In the display next to the temperature key, it is possible to read the current value (0 – 120).
In the display next to the time key, it is possible to read the set point.