Manual EN
Uninterruptible Power Supply
V 1.0
Charge and control units
BLOCK Transformatoren-Elektronik GmbH
Max-Planck-Strasse 36-46, 27283
.
Verden, Germany
31.08.20 / SCH
Subject to technical changes
5
3.1
Block Circuit Diagram
The following block circuit diagram depicts a wiring example.
In order to ensure good communication between the battery module and the charge and
control unit, the chosen interfaces, control and signal lines should be < 3 meters.
In addition, ensure that the control line is not routed parallel to the power cables, otherwise
there is a likelihood of communication disruptions.
Illustration 2: Block circuit diagram of wiring
To achieve the maximum buffer time, up to 3 battery modules can be installed in parallel (see
Chapter 4.5).
When multiple battery modules are used, a control line is affixed to one battery module only.