大型风扇行业的领航者
Pre-Installation
3.1 3.1
Check lists before installation
Installation Tools
Level; Pliers; Cable Cutters; M8-M10 (2 sets outer hexagonal wrench); Scissor Lift or
Scaffold; Wrench 4 sets; Phillips Screwdriver; Electric Drill; M4.2 bit;
Torque Wrench; M8-M30 Socket Wrench
Typical mounting methods
Each type of building structure requires a specific mounting bracket, BloBlades
Fans can
only be hung from standard mount with an I-beam or concrete beam. For
buildings with
glulam beams (laminated wood), an additional set of brackets is required
and can be purchased separately. Consult a structural engineer for installation methods.
1)
Verify with the contractor, building owner, or structural engineer to ensure the building
structure is sound and adequate to support the load prior to fan installation.
2)
Take measurements of the height of the bottom of I-beam and blade level.
3)
Check if you have the correct power circuit for the fan.
3.2 General Mounting Considerations
CAUTION:
Bloblades Fans product warranty will not cover equipment damage
or
failure that is caused by improper installation.
3.2.1 Weight
A standard six blade 24' fan which is the biggest fan is about 276lbs. In applications
where the
Motor is inverted to below upward (very unusual) there is an additional down
force of 110lbs. Due to fan thrust. If there is any doubt of this, a professional structural
engineer should perform a thorough evaluation of the building prior to purchasing fans
BloBlades Fans can only be hung from an I-beam or concrete beam and angle irons on
main structure of building. Do not mount the fan to single purlins, trusses, or bar
joists. Consult a structural engineer for installation methods not covered in the manual.
9