Installation Manual
BlinkCharging.com
•
(888) 998.2546
16
using a vacuum cleaner or air blower. The cabinet can be cleaned using a vacuum cleaner. The dust on the
components can be cleaned using a soft cloth. Please pay extra attention while using the vacuum cleaner, it
should not apply pressure on the control boards or any components.
REPLACEMENT OF FIXED-LIFE COMPONENTS
To prevent the device from failure due to worn out components, it is necessary to replace the components
before they reach the end of their lifespan. Use the following replacement intervals as a guideline for the
estimate of the total running time. Please contact a Tellus service representative for further assistance when you
replace the parts.
•
Intake and exhaust air filters (if present): Approximately three (3) years. The period depends upon the site
conditions.
•
Please keep in mind that the replacement interval of each part can vary depending on, for example, the
usage environment of the device.
11. TROUBLESHOOTING
ERROR CODES
If an error occurs, check the nature of the error by referring to following “Error Code List” and take
appropriate actions according to instructions by the manufacturer.
ERROR
DESCRIPTION
POSSIBLE SOLUTION
ERROR FLAG 0
Lightning protection device failure
Check the SPD and GFCI circuit
ERROR FLAG 1
Insulation detection abnormal
The insulation check on the EV has failed. Please try
to charge different EV.
ERROR FLAG 2
Abnormal communication between Insulation
Monitor and Main Control Board (CM)
Please check the connection between the IM and CM
boards. Check the LED lights on the CM and IM
ERROR FLAG 3
Abnormal communication between TR board
and CM board
Please check the connection between the tr and cm
boards. Check the LED lights on the CM and TR
ERROR FLAG 4
Electronic lock failure
Possible failure of the gun to lock on the EV or the
24v supply voltage
ERROR FLAG 5
Internal use
Reserved
ERROR FLAG 6
Abnormal communication between DC meter
and Main Control Board (CM)
Please check the connection between the DC and
CM boards. Check the LED lights on the CM and
communication lines of DC meter.