8
9
Charge on.
Charge on.
Figure 3-2. Prepare for Wiring
1. Connect the electrical wiring to the Blink Charger.
a. Choose the appropriate conduit in accordance with all applicable state, local and national electri-
cal codes and standards.
b. Use No. 8 AWG, 75°C or 90°C copper wire with Listed pressure terminal connectors, such as
ring and fork types, on the end of the conductor before attachment to the terminal blocks and
17.7 lb-in Torque force when connecting to Input terminal block.
3.3 Install the Charger
1. Drill bolt holes in the wall for the mounting bracket and the cable hanger.
Note:
Follow applicable accessibility requirements for the mounting position. The unit shall be mounted at a
sufficient height from grade such that the height of the storage means for the coupling device is located between
24 inches (600 mm) and 4 feet (1.2 m) from grade per NEC Article 625.
Masonry Walls
Sheet Rock and Wood Stud Walls
Figure 3-1. Mounting Bracket
2. Secure the main body mounting bracket and the cable hanger bracket to the wall with appropriate bolts,
as follows:
a. For masonry walls, use ¼” expansion bolts.
b. For finished walls supported by wood studs, use #10 x 2.5” Countersunk Phillips Head Wood
Screws.
c. Attach cable hanger to wall below mounting bracket with appropriate screws or anchors.