25.
Object 1017h: Producer heartbeat time
The producer heartbeat time shall indicate the configured cycle time of the heartbeat.
Identifier 600h + current CAN ID
Default 615h
Byte 0
40h
Read Device Register
2B
Set device register
Byte 1
17h
CAN Object 1017h
Byte 2
10h
Byte 3
00h
Sub index
Byte 4
YYh
YYh: Heartbeat time in milliseconds
MSByte
Byte 5
XXh
XXh: Heartbeat time in milliseconds LSByte
Byte 5, 7
00h
Not used
Heartbeat time: XXYYh (from 000Ah to FFFEh: 10ms to 65534 ms)
Examples:
Direction
Identifier Format Message
Data
To Keypad
615
Std
40 17 10 00 00 00 00 00 Read heartbeat time
Keypad Reply
595
Std
4B 17 10 00 64 00 00 00 Heartbeat time = 100ms
To Keypad
615
Std
2B 17 10 00 00 00 00 00 Switch off the heartbeat
Keypad Reply
595
Std
60 17 10 00 00 00 00 00
To Keypad
615
Std
2B 17 10 00 32 00 00 00 Set heartbeat time =
50ms
Keypad Reply
595
Std
60 17 10 00 00 00 00 00
To Keypad
615
Std
2B 17 10 00 F4 01 00 00 Set heartbeat time =
500ms
Keypad Reply
595
Std
60 17 10 00 00 00 00 00
Heartbeat message
The heartbeat mechanism for a CANopen device is established by cyclically transmitting the
heartbeat
message by the heartbeat producer. One or more CANopen devices in the network are
aware of this
heartbeat message. If the heartbeat cycle fails for the heartbeat producer the local
application on the
heartbeat consumer will be informed about that event.
If a CANopen device starts with a value for the heartbeat producer time unequal to 0 the
boot-up message is regarded as first heartbeat message.
Identifier
700h + current CAN ID
Default 715h
Byte 0
XXh
XXh: State of heartbeat producer
00h: Boot-up
04h: Stop
05h: Operational
7Fh: Pre-operational
Example: