0 LANGUAGE SELECTION:
This selects the language of the
operating menu ( English, German, Spanish, Portuguese) )
1 I-CONVERTER PRIM
: This selects the primary current of the
current converter. Adjustment is via the
é
/
ê
keys.
(5...7500A) Save and continue with ENTER
2 I-CONVERTER SEC
: This sets the secondary current of the current
converter.(5A or 1A possible). Selection via
é
/
ê
. Save
and continue with ENTER
3 END STOPP
: By setting the end stopp, the number of active
capacitor branches is matched to the respective
capacitor bank. This is done via the
é
/
ê
keys. The visible
symbols of the capacitors correspond to the connected
outputs. The setting is confirmed and saved with ENTER.
4 CONTROL SERIES
: The ratio of the capacitor branch powers
determines the control series, the power of the first
capacitor always being assigned the value 1. The control
series required for the compensation network is again
selected via the
é
/
ê
keys. The selected series is entered
with the ENTER key, which also takes the user to the next
step.
5 CONTROL PRINCIPLE
: Control preference may be selected here:
þ
SEQUENTIAL connection
þ
LOOP connection
þ
INTELLIGENT loop connection
(default )
See Section 8 for an explanation of the various control
modes.
Selection with
é
/
ê
keys and confirmation with ENTER
leads to the next point:
6 POWER 1. STAGE
: To determine the controller's response
sensitivity, the dimensions of the network's smallest
capacitor (stage 1) must be known. They are entered in two
steps in kvar. The integral kvar values (before the comma)
are initially selected via the
é
/
ê
keys and saved with
ENTER. The positions after the comma are then selected,
again via the
é
/
ê
keys. Saving with ENTER..