www.blaubergventilatoren.de
KoMFort erv ec dB
11
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER’S LABEL.
• The unit is rated for connection to 1~230 V/50 Hz according to the wiring diagram.
• The connection must be made using insulated conductors (cables, wires).
• The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending
on the wire type, insulation, length and installation method.
• The external power input must be equipped with an automatic circuit breaker QF built into the stationary wiring to open the circuit
in the event of overload or short-circuit.
• The position of the automatic circuit breaker must ensure free access for quick power-off of the unit.
• The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the “Technical
data” section or to the unit label).
• It is recommended to select the nominal current of the circuit breaker from the standard series, following the maximum current of
the connected unit.
• The circuit breaker is not included in the delivery set and can be ordered separately.
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
L
N
PE
PK
PK
+U
0-10V
GND
NO
C
GND
Tx
Rx
+U
SM-L
SM-N
L
N
QF
230 V AC
РЕ
2
1
2
1
3
+U
2
GND
1
0-10V
-
Tx
Rx
+
L1
N
SM1
L1
N
SM2
L
N
QF
230 V AC
РЕ
SM1
SM2
EXHAUST
External wiring diagram
SUPPLY
Electric actuators of
outer air dampers
Control panel
External
sensor N.O.
contact
Humidity
sensor
N.C. contact
from fire alarm
panel. Remove
the jumper