16
www.blaubergventilatoren.de
KOMFORT EC LB/LBE S11
Function
Indication
9
Language selection
To select the control panel interface language select the LANGUAGE
submenu from the Engineering menu and press ENTER
.
Select the desired language from the list.
Press ENTER
.
To return to the Engineering menu without saving changes press EXIT
.
10 Extra options
Select the EXTRA OPTIONS submenu from the Engineering menu and
press ENTER
.
The SUPPLY FAN OFF mode helps to prevent heat exchanger freezing
and requires disabling of the HEATING CONTROL parameter.
To activate the heat exchanger freezing protection function by means of
the supply fan deactivation set the HEATING CONTROL parameter value
to OFF. To proceed to the function setup set the SUPPLY FAN OFF MODE
parameter to ON.
To select a humidity sensor type set 1 for the duct sensor (exhaust duct)
or 2 for the room sensor in the HUMIDITY SENSOR SELECTION menu item.
For selecting the bypass operation mode set 1 in the BYPASS
OPERATION MODE to select the regular operation mode, which prevents
heat exchanger freezing, or 2 to enable bypass opening in the ventilation
mode.
To save the changes and return to the Engineering menu press EXIT
.
If the SUPPLY FAN OFF MODE parameter is set to ON the control panel
switches to the SUPPLY FAN OFF MODE setting.
Select an item by touching the respective field: WORKING HOURS,
DOWNTIME and SWITCH-OFF TEMPERATURE (the temperature is set
according to the outdoor temperature sensor readings defined in the range
from 0 °C to -30 °C).
Then use
or
buttons to set the desired value.
Press ENTER
to confirm the parameters.
To return to the Engineering menu without saving changes press EXIT
.
11 Password change
Select the PASSWORD CHANGE submenu from the Engineering menu
and press ENTER
.
Then enter the new password for accessing the Engineering menu.
Press OK.
To re-enter the password press RESET
. This operation clears the
ENTER NEW PASSWORD field.
To return to the Engineering menu press EXIT
.
Table 6. Unit control and adjustment of operating parameters of the unit